Télécharger Imprimer la page

Rockwell Automation Allen-Bradley 140MG-H E Serie Mode D'emploi page 5

Publicité

6
Dip LSIG Trip Unit
In (A)
0,2
25
5
60
12
140G-H
100
20
125
25
*
160
32
40
8
60
12
140G-J
100
20
150
30
250
50
7
Dip LSIG Trip Unit
Neutral setting
Always
3p
Always only by means of System Bus
Always only by means of System Bus
Always only by means of
4p
Always only by means of dip switches
Example - Esempio - Beispiel - Exemple - Ejemplo
Dip switches setting example
with 4p:
Publication 140G-IN100E-EN-P - November 2020
Trip Unit Protection Settings Adjustment for 140G-H, 140G-J, 140MG-H, 140MG-J
Protection G- Protezione G- Schutzfunktion G - Proteção G- Protección G - G
I4 (In)
0,25
0,45
0,55
0,75
6,25
11,3
13,8
18,8
15
27
33
45
25
45
55
75
31,3
56,3
68,8
93,8
40
72
88
120
10
18
22
30
15
27
33
45
25
45
55
75
37,5
67,5
82,5
113
62,5
113
138
188
(*) IEC ONLY
Ekip T&P or System Bus
Ne=ON; 50%
Example - Esempio - Beispiel - Exemple - Ejemplo
In = 100A
I4 = 100x(0,2+0,25)=45A
t4 = 0,2s @ I>I4
0,8
1
20
25
48
60
80
100
100
125
128
160
32
40
48
60
80
100
120
150
200
250
Setting Neutral - Settaggio Neutro - Einstellung Neutralleiter -
Réglages Neutre - Configuraciones Neutro - 设定频率和中性
Default setting
ON; 100%
ON; 100%
DIR 1000721R0506 (Version 04)
5

Publicité

loading