Dimensions
GENERAL INSTALLATION INSTRUCTIONS
⚠ Installation must be carried out by qualified and experienced personnel in compliance with applicable regulations.
Preliminary checks
⚠ Before installing the operator:
• Provide a suitable single-pole disconnection device, with a maximum of 3 mm between the contacts, to disconnect the power supply;
• Prepare suitable piping and ducts for routing the electrical cables, ensuring protection against mechanical damage;
• Prepare a drain pipe to prevent stagnation that may cause oxidation;
•
Make sure that any connections within the container (made to ensure the continuity of the protection circuit) are fitted with additional insulation
compared to the other internal conductor parts;
• Make sure the gate structure is sturdy enough, that the hinges are in proper working order and that there is no friction between the moving and fixed parts;
• Make sure there are opening and closing mechanical stops.
Types of cables and minimum thicknesses
Connection
Control panel power supply 230 V
Motor power supply 230 V
Flashing light
Photocell transmitters
Photocell receivers
Control and safety devices
Encoder
Antenna
N.B. : If the cables differ in length from what shown in the table, the cable cross-section is determined according to the actual current draw of the devices
connected and according to the provisions of the IEC EN 60204-1 standard.
For connections that require several, sequential loads, the sizes given on the table must be re-evaluated based on actual power draw and distances. When
connecting products that are not specified in this manual, please refer to the documentation provided with said products.
570
580
100
~ 850
Cable
Cable length
type
1< 15 m
3G x 1,5 mm 2
4G x 1,5 mm 2
H05RN-F
2 x 0,5 mm 2
2 x 0.5 mm 2
FROR CEI
20-22
4 x 0.5 mm 2
IEC EN
2 x 0.5 mm 2
50267-2-1
TWISTED
RG58
Cable length
15 < 30 m
3G x 2,5 mm 2
4G x 2,5 mm 2
2 x 1,5 mm 2
max 30 m
max 10 m