Dual-Circuit Occupancy
Sensing Switch
MS-OPS6-DDV
MS-PPS6-DDV
UMS-OPS-DDV
UMS-PPS6-DDV
Occupancy
Partial-ON only
Single-pole only
Two circuits, each rated at:
Lighting
(incandescent, halogen, CFL, LED, ELV, MLV,
electronic fluorescent, magnetic fluorescent)
120-277 V~ 50 / 60 Hz 6 A
Fan
120 V~ 50 / 60 Hz 4.4 A 1/6 HP
Combined lighting and fan load
120 V~ 50 / 60 Hz 4.4 A
P/N 032555 Rev. A 05/2019
English
Circuit 1
Tap Button
Top
programming
button
Bottom
programming
button
Circuit 2
Tap Button
Major motion coverage:
30 ft × 30 ft (9 m × 9 m) [900 ft
2
(81 m
Minor motion coverage:
20 ft × 20 ft (6 m × 6 m) [400 ft
2
(36 m
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 U.S.A.
www.lutron.com
®
All manuals and user guides at all-guides.com
Important Notes
Please read before installing.
®
1. A ground connection is required for product
to function. Connect green-sleeved wire
to ground only in retrofit and replacement
applications. When neutral connection is
available, remove green sleeve and connect
to neutral. If neither wire is present, consult
a licensed electrician.
2. Device will not function if Black wires
(Circuit 1/Line 1) are not wired.
3. This product is rated to control 6 A per
circuit. Circuits may NOT be wired in
parallel to control loads greater than 6 A.
4. CAUTION: Risk of Electric Shock —
More than one disconnect switch may be
required to de-energize the equipment
before installing the unit, rewiring, or
replacing bulbs.
5. When power is applied, the dual-
circuit sensing switch can be manually
turned on or off after 60 seconds and
will automatically control the load after
2 minutes.
6. The dual-circuit sensing switch requires
an unobstructed view of the room and
line-of-sight to detect motion.
7. Hot objects or moving air currents can
affect the performance of the dual-circuit
sensing switch and may cause the sensor
to turn on unexpectedly or maintain its
current state longer than desired.
8. CAUTION: To reduce the risk of
overheating and possible damage to
other equipment, DO NOT use to control
receptacles.
9. Install in accordance with all national and
local electrical codes.
10. For indoor use only. Operate between 32 °F
and 104 °F (0 °C and 40 °C).
11. DO NOT exceed 20 devices at 120 V~ or
7 devices at 277 V~ on a single branch
circuit.
12. Clean with a soft damp cloth only. DO NOT
use any chemical cleaners.
2
)]
2
)]
Warranty:
http://www.lutron.com/TechnicalDocumentLibrary/Sensor_Warranty.pdf
Lutron and Maestro are trademarks or registered trademarks of
Lutron Electronics Co., Inc. in the US and/or other countries.
© 2013–2019 Lutron Electronics Co., Inc.
Wiring
1
Turn power OFF
WARNING! Shock Hazard. May result in serious injury or death. Turn power OFF at circuit
breaker(s) before installing the unit, rewiring, or replacing bulbs.
A.
B.
O
O
OR
O
Single-Line
Two-Line*
* Wiring must comply with NEC code for wiring Multiple Branch Circuits: Where two or more branch circuits
supply devices or equipment on the same yoke, a means to simultaneously disconnect the ungrounded
conductors supplying those devices shall be provided at the point at which the branch circuits originate.
2
Connect dual-circuit sensing switch
A. When neutral is present in outlet box: remove green sleeve, connect white wire to neutral.
Single-Line Wiring
Black
1
Black
Black-
Black-
120–277 V~
Orange
Orange
Bare
White
Ground
2
Neutral
B. If no neutral is present, connect green-sleeved wire to ground.
Single-Line Wiring
Black
1
Black
Black-
Black-
120–277 V~
Orange
Orange
Bare
Green-sleeved wire
Neutral
Ground
2
1
Device will not function if Black wires (Circuit 1/ Line 1) are not wired.
2
Device will not function if it is not grounded.
NOTE: Leave wallplate off if custom settings are desired. See Custom Settings instructions on reverse side.
3
Turn Power ON
A.
B.
O
OR
O
O
4
Wait for 60 seconds before manual switching
• The sensing switch will not manually control the load for 60 seconds.
5
Wait for an additional 60 seconds for automatic switching
• Once power has been restored, the sensing switch will not
automatically control the load for the first 2 minutes.
O
O
O
Two-Line Wiring
Load 1
Line 1
Black
1
120–277 V~
Load 2
Line 2
Black-
Orange
120–277 V~
Bare
White
Neutral 2
Ground
2
Neutral 1
Two-Line Wiring
Load 1
Line 1
Black
1
120–277 V~
Load 2
Line 2
Black-
Orange
120–277 V~
Bare
Green-sleeved wire
Ground
Neutral 2
Neutral 1
O
O
O
Black
Load 1
Black-
Load 2
Orange
Black
Load 1
Black-
Load 2
Orange
2
60 s
60 s