AXIS A1601 Network Door Controller
Function
Pin
1
DC ground
(GND)
2
NO
3
COM
4
NC
Relay power jumper
When the relay power jumper is fitted, it connects 12 V DC or 24 V DC to the relay COM pin.
It can be used to connect a lock between the GND and NO, or GND and NC pins.
Power source
DC IN
PoE
1.
The power is shared between the two relays and AUX I/O 12 V DC.
NO
NO TICE
NO
TICE
TICE
If the lock is non-polarized, we recommend you to add an external flyback diode.
Auxiliary connector
Use the auxiliary connector with external devices in combination with, for example, motion
detection, event triggering, and alarm notifications. In addition to the 0 V DC reference point and
power (DC output), the auxiliary connector provides the interface to:
Notes
Normally open.
For connecting relay devices. Connect
a fail-secure lock between NO and DC
ground.
The two relay pins are galvanically
separated from the rest of the circuitry
if the jumpers are not used.
Common
Normally closed.
For connecting relay devices. Connect
a fail-safe lock between NC and DC
ground.
The two relay pins are galvanically
separated from the rest of the circuitry
if the jumpers are not used.
Max power at 12 V DC
1 600 mA
800 mA
24
Specifications
0 V DC
Max current = 2 A per
relay
Max voltage = 30 V DC
1
Max power at 24 V DC
800 mA
400 mA
1