UL: Supervised inputs were not evaluated by UL for burglary use. Only door monitor and REX
support supervision with end of line resistors.
Note
We recommend using twisted and shielded cables. Connect shielding to 0 V DC.
Door connector
Two 4-pin terminal blocks for door monitoring devices (digital input).
Door monitor supports supervision with end of line resistors. If the connection is interrupted, an
alarm is triggered. To use supervised inputs, install end of line resistors. Use the connection
diagram for supervised inputs. See .
Function
Pin
1, 3
DC ground
2, 4
Input
Important
The qualified cable length is up to 200 m (656 ft) if the following cable requirement is
met: AWG 24.
Relay connector
Two 4-pin terminal blocks for form C relays that can be used, for example, to control a lock or
an interface to a gate.
AXIS A1601 Network Door Controller
Notes
For communicating with door monitor.
Digital input or Supervised input —
Connect to pin 1 or 3 respectively to
activate, or leave floating (unconnected)
to deactivate.
23
Specifications
0 V DC
0 to max 30 V DC