WIKA GDM-100-TI Mode D'emploi page 16

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Commissioning, operation
Capacitive load
With capacitive loads elevated switch-on currents arise. These can be reduced by
series-connecting resistors in the supply line.
EN
Examples: Contact protection measure with current-limiting resistor
U
B
5.3 Electrical mounting of the transmitter
Requirements for voltage supply
Power supply: DC 10 ... 30 V
The supply must be made via an energy-limited circuit in accordance with IEC 61010-1.
Requirements for electrical connection
Cable diameter matches the cable bushing of the mating connector.
Cable gland and seals of the mating connector are correctly seated.
With cable outlets, no humidity can ingress at the cable end.
Requirement for shielding and grounding
The transmitter is grounded via the process connection of the gas density monitor. The
transmitter is connected with the process connection of the gas density monitor via the
mounting.
Pin assignment
Transmitter, angular connector (2-pin)
16
R
1
Load
UB+/Sig+
+
U
-
0V/Sig-
WIKA operating instructions, models GDM-100-TI, GDM-100-TA
U
B
R
A
1
Load

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Gdm-100-ta

Table des Matières