For the Installer
6.3 I
D
NSTALLING THE
UCTWORK AND THE REGISTERS
• Never install a stale air exhaust register in a closed room where a combustion device operates, such as a gas
furnace, a gas water heater or a fireplace.
• When performing duct connections, always use approved tools and materials. Respect all corresponding laws
and safety regulations. Please refer to your local building code.
6.3.1 F
D
S
ULLY
UCTED
YSTEM
Stale air exhaust ductwork:
Install registers in areas where contaminants are produced: Kitchen, bathrooms,
laundry room, etc.
Install registers on an interior wall, 6 to 12 inches (152 to 305 mm) away from the
ceiling OR install them in the ceiling.
Install the kitchen register at least 4 feet (1.2 m) away from the range.
Fresh air distribution ductwork:
Install registers in bedrooms, dining room, living room and basement.
Install registers either in the ceiling or high on the walls with the airflow directed
towards the ceiling.
If a register must be installed in the floor, direct the air flow up the wall.
6.3.2 E
D
S
XHAUST
UCTED
YSTEM
When performing duct connections to the furnace supply
duct, use metal ducts appropriately sized to support the
additional airflow produced by the unit.
Stale air exhaust ductwork:
Install registers in areas where contaminants are produced: Kitchen, bathrooms,
laundry room, etc.
Install registers on an interior wall, 6 to 12 inches (152 to 305 mm) away from the
ceiling OR install them in the ceiling.
Install the kitchen register at least 4 feet (1.2 m) away from the range.
Fresh air distribution ductwork:
Cut an opening into the furnace supply duct at least 18 inches (0.5 m) away from
the furnace.
Connect this opening to the fresh air distribution port of the unit (use metal ducts,
see illustration at right).
Make sure that the duct forms an elbow inside the furnace ductwork.
NOTE : For this type of installation, it is recommended, however, not essential, that the
furnace blower be synchronized with the unit.
6.3.3 E
D
S
XHAUST
UCTED
YSTEM
Stale air exhaust ductwork:
Install registers in areas where contaminants are produced: Kitchen, bathrooms,
laundry room, etc.
Install registers on an interior wall, 6 to 12 inches (152 to 305 mm) away from the
ceiling OR install them in the ceiling.
Install the kitchen register at least 4 feet (1.2 m) away from the range.
Fresh air distribution ductwork:
Cut an opening into the furnace return duct not less than 10 feet (3.1 m) away
from the furnace (A+B).
Connect this opening to the fresh air distribution port of the unit (see illustration
at right).
NOTE : For this type of installation, it is recommended, however, not essential, that the
furnace blower be synchronized with the unit.
- S
S
UPPLY
IDE
CAUTION
- R
S
ETURN
IDE
WARNING
VH0077
VH0130
VH0131
8
18" (0.5
)
M
MINIMUM
A
B
A + B =
AT LEAST
10' (3.1
)