command. The Electric Lock (LOCK A+) will be automatically turned ON
each time the gate opens.
If the DIP8 is OFF, the Electric Lock command is DISABLED.
MANUAL RELEASE FACILITY
The DIP 9 in the ON position enables the Manual Release Facility.
Once the gate has completely closed or opened, a short reversal
manoeuvre (0.2 seconds) will be done to ease manual release (current
sensors in this phase are not enabled).
ELECTRIC LOCK unlocking FACILITY
The DIP 9 in the ON position enables the Electric Lock unlocking
Facility. From close position, just before opening, the gate will perform
a short closing manoeuvre (0.5 seconds) to ease unlocking from
electric lock.
ELECTRIC LOCK coupling FACILITY
The DIP 10 in the ON position enables the Electric Lock coupling
Facility. Once the gate has closed, a short hammering close pulse (0.5
seconds) will be done at full power to guarantee the electric lock or
mechanical bolt coupling (the current sensors in this phase are not
enabled).
GATE FUNCTIONING AFTER A BLACKOUT
(in case back-up batteries are not installed)
It's recommended to close completely the gate manually when the main
AC power resumes. Only in the closing position of the gate the control
board realigns itself.
In case the gate is already closed, no need of special procedures, the
gate is ready to work.
In case the gate is completely opened and the Automatic Closing is
enabled (DIP3 in ON position), countdown of Automatic Closing will
start automatically the moment AC power is available.
During this phase all the safety devices (photocells and safety strip) are
active.
PHOTOCELL (PHOT - COM)
In case the switch DIP4 is in the OFF position, the photocells are active
both during gate opening and during gate closing. In this configuration,
if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening
when the obstacle is removed
- while the gate is still, it will not move neither in opening nor in closing.
In case of the switch DIP4 is in the ON position, the photocells are
active only during gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will
remain still if a close command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the
photocell receivers must be connected in series.
In case the photocells are not installed, this contact must be short
circuited with a wire jump (from PHOT to COM) to permit the gate to
operate.
SAFETY STRIP (EDGE - COM)
If an obstacle presses the safety strip:
- while the gate is still, it will not move neither in opening nor in closing
- while the gate is closing, the gate will open
- while the gate is opening, the gate will close.
In case the safety strip is held pressed a further quick reversion, after 2
seconds, is performed. The gate interrupts any movement and this
alarm state is indicated by 1 minute Blinker flashing. The normal gate
operations can be restored by pressing any push button or radio
commands.
The safety strip input (EDGE - COM) is a NORMALLY CLOSED
contact.
In case there are more than one safety strip, all their contacts must be
connected in series.
In case the safety strip is not installed, this contact must be short
circuited with a wire jump (from EDGE to COM) to permit the gate
to operate and the Safety Strip test must be disabled (JP4
OPENED).
TESTING THE SAFETY STRIP EQUIPMENT
The JUMPER JP4 CLOSED enables to test the safety strip equipment.
The test is performed every time the gate completes a full opening. The
test is available only if the safety strip device is equipped with a
dedicated power supply input.
In fact, the safety strip equipment power supply input can be connected
to the A+TEST and A- outputs (JP4 closed). Automatically, every time
the gate completes a full opening, just before closing, the control board
switches OFF the A+TEST and A- power supply output for a very short
time. While the safety strip power supply is switched OFF, if everything
is working fine the safety strip contact (EDGE - COM) must open. In
case the test fails, no other gate manoeuvre will be allowed.
NOT ALL THE
SAFETY STRIPS CAN
JUMPER JP4 MUST BE LEFT OPEN.
FLASHING LIGHT (BLINKER - A+)
Connect the flashing light to outputs A+ and BLINKER, use flashing
lights ACG7061 and 24V bulbs of 20W maximum.
N.B.: This electronic PK2-24V board can only supply power to
FLASHING LIGHTS with inbuilt flashing circuit.
PRE-FLASHING FUNCTION
The DIP 5 in the ON position enables the pre-flashing, the FLASHING
LIGHT starts blinking 3 seconds before every movement of the gate.
The DIP 5 in the OFF position disables any pre-flashing, the FLASHING
LIGHT and the motors will star at the same time.
CURRENT SENSOR ALARM
The CURRENT SENSOR, permits the obstacle detection. In fact,
during opening or closing of the gate, if any of the gate leaf finds an
obstacle, the gate reverses its movement. The obstacle detection
sensitivity can be adjusted on each motor, by the trimmers M1 and M2
(POINT C).
Should the sensor detect another obstacle during the reverse
movement, the gate will reverse another time for just 1 second and then
stop. This ALARM STATE is indicated by the FLASHING LIGHT that
blinks for 1 minute. The normal gate function can be restored pressing
any push button or radio commands.
GATE OPEN INDICATOR (SIGNAL - COM)
Should you need to have an indication about the leaf position, the
output SIGNAL - COM can be connected to a 12Vdc bulb of 3W
maximum. It is turned ON when the gate is open or partially open, it is
turned OFF only when the gate is completely closed.
WE RECOMMEND NOT TO OVERLOAD THE INDICATOR OUTPUT
(SIGNAL - COM) OTHERWISE THE GATE FUNCTIONING COULD BE
COMPROMISED OR THE CONTROL BOARD COULD BE DAMAGED.