(Residential, commercial and
ight industry class).
Important: The unit's compliance with the above standards does not guarantee
the compliance of the installation as a whole (several other factors not relating to
the unit may be involved). As a result, the installer must observe the applicable
recommendations in order to guarantee compliance.
EN
Power to the electric heaters should be cut and post-ventilation activated whenever
the fan motor assembly is stopped intentionally or unintentionally.
allows post ventilation of the comfort unit for at least 2 minutes.
To ensure the hot water and electrical heaters work correctly when used
simultaneously, we recommend only low temperature settings are used to ensure
our safety devices operate correctly.
Two thermostats protect units equipped with heaters from accidental overheating:
- The manual temperature limiter (Fig.15, a)
- The automatic temperature limiter (Fig.15, b) always located next to the electrics
box.
Do not reset (Fig.15, c) these thermostats until the potential causes of the overheating
have been checked:
Never connect several fan coil unit motors in parallel on the same
thermostat.
The unit can be manually reset by inserting a screwdriver in the hole (Fig.15, c)
The unit must be serviced periodically between the heating and cooling seasons.
In particular, components prone to clogging (filter, condensate drain pan, coil, etc.)
must be checked.
from hot pipes.