Télécharger Imprimer la page

Mitsubishi A2 Serie Manuel Du Materiel page 95

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 232
α
2 Simple Application Controllers
2) Remove the top cover from the jumper area and move the jumper to the pins labeled 450°C
as in "Hardware Setup" below.
Figure 13.7: AL2-2TC-ADP Gain Adjustment
3) Turn the power on and select "Others..." from the TopMenu while in Stop Mode.
4) After setting the mode to "TC" (See the Offset Adjustment description above.), select
"Calibrate" from the Analog input settings menu.
5) Select "450°C" from the Calibrate menu as in "Controller Setup" in the figure above. There
should be a confirmation message that reads "OK." If not, refer to the Applicable Error
Checks section below. This completes the gain calibration procedure. To calibrate the gain
for channel 2, repeat the steps above replacing L1-, L1+ and SLD with L2-, L2+ and SLD
respectively. When the calibration is finished, move the jumper to the "LINE" pins.
Figure 13.8: Jumper position after calibration
It is usually necessary to perform the Offset Adjustment when performing the Gain
Adjustment. See section 12.4.3 for more details.
Hardware Setup
450°C
450°C
L1+ L1- SLD
Hardware Setup
Controller Setup
Ca l i b r a t e
- 5 0 ° C
4 5 0 ° C
LINE
LINE
AL2-2TC-ADP 13
ENG
OK
ENG-81

Publicité

loading