2 Simple Application Controllers
12.4.2
Wiring
Caution
• Please use an isolated Power supply and turn off the Power before any wiring operation
is performed.
• Input and Output cables should not be run through the same multi core cable or share
the same wire.
• Input cable (from sensor to AL2-2PT-ADP) must be less than 10m (32'81'') and the
output cable length must be less than 3m (9'10").
• The wire should be used as a single cable or the multi core wires (can be used with a
crimp terminal) should be carefully twisted together.
Do not connect a soldered wire end to the AL2-2PT-ADP.
• To avoid damaging the wire, tighten to a torque of 0.5 ~ 0.6 N⋅m.
• The AL2-2PT-ADP should be adjusted for offset and gain purposes, therefore, turn off
the Power before performing the adjustment wiring.
Figure 12.4:Wiring
24V
DC
0.5A
24+
AL2-2PT-
ADP
Grounding
resistance
100Ω or less
24-
V1+
V1-
V2+
100kΩ
100kΩ
100kΩ
+15V
5V
5V
4.7kΩ
4.7kΩ
L1
L1-
I1-
L2+
L2-
+
PT100 Sensor
PT100 Sensor
1.0A
V2-
+
-
100kΩ
5V
4.7kΩ
4.7kΩ
AL2-10MR-D
AL2-14MR-D
I2-
AL2-24MR-D
Grounding
resistance
100Ω or less
AL2-2PT-ADP 12
(A) (B) 1
2
ENG-65