Télécharger Imprimer la page

Mitsubishi A2 Serie Manuel Du Materiel page 72

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 232
α
2 Simple Application Controllers
11.3.2
Wiring
Caution
• Turn off the Power before performing any wiring operations.
• The Output cables should not be run through the same multi core cable or share the
same wire.
• The wire should be used as a single cable or the multi core wires (can be used with a
crimp terminal) should be carefully twisted together.
Do not connect a soldered wire end to the
• The Output cable length must be less than 30 m (98' 5")
• To avoid damaging the wire, tighten to a torque of 0.5 ~ 0.6 Nm.
• The connectors must be covered to prevent contact with "Live" wires.
Figure 11.3:Wiring in Voltage output mode
Note: "+" and "-" terminals are nonreversible.
DC/DC converter
AL2-2DA
Figure 11.4:Wiring in Current output mode
Note: "+" and "-" terminals are nonreversible.
DC/DC converter
AL2-2DA
Table 11.5: Wiring Notation
Item
1
Grounding resistance of 100Ω or less
2
In the case of apparent excess noise please connect a 0.1-0.47µF capacitor
3
External equipment such as an Inverter, etc.
4
External 24VDC power supply
5
External equipment such as a Record meter, etc.
4
24V DC
1.0A
+
-
VO+
2
IO+
VIO-
1
4
24V DC
1.0A
+
-
VO+
IO+
VIO-
1
AL2-2DA (AL2-14MR-*, AL2-24MR-*) 11
α
2 Series Controller.
3
5
Description
ENG-58

Publicité

loading