GE RAK149P2 Manuel Du Propriétaire Et Instructions D'installation page 9

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Configuration mode
3. Temperature Differential—Stage 1—(1–9°F)
(1–5°C)
Set the number of degrees between the
"setpoint" temperature and the
"turn on" temperature for first stage.
Press the
Press the HOLD button to advance to the next screen.
Note: Default factory setting is 2°F/1°C for each stage.
4. Temperature Differential—Stage 2 (1–9°F/1–
5°C) Heat Pump (HPb) only
Set the number of degrees between when
stage 1 turns on and stage 2 turns on.
Press the
value.
Press the HOLD button to advance to the next screen.
Note: Default factory setting is 2°F/1°C for each stage.
5. Minimum Cool Setpoint (60, 64, 66, 68, 70,
72, 74, 76°F) (15, 17, 19, 20, 21, 22, 23, 24°C)
Adjust to control the minimum Cool set
temperature allowed.
Press the
Press the Hold button to advance to the next screen.
Note: Default factory setting is 60°F/15°C.
6. Maximum Heat Setpoint (65, 70, 72, 74, 76, 78, 80, 85°F) (18, 21, 22,
23, 24, 26, 27, 29°C)
Adjust to control the maximum Heat set
temperature allowed.
Press the
Press the Hold button to advance to the next
screen.
Note: Default factory setting is 85°F/29°C.
7. Room temperature offset (+9°F
to –9°F) (+5°C to –5°C)
Adjust to calibrate displayed room temperature
to match actual room temperature.
Press the
Press the Hold button to advance to the next screen.
Note: Move the Function switch to Heat or Cool position to lock the
settings into memory.
Note: Default factory setting is 0°F/0°C.
49-5000517 Rev. 3