Sanyo SGP-M2 Manuel D'installation page 24

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 39
Over 35 cm
Refrigerant tubing side
Over 60 cm
Over
10 cm
Over
Over
Over 1 m
10 cm
10 cm
Fig. 1
(3) In snowy regions, be sure to install a snow-protection hood and enclosure.
Even in regions that do not have heavy snowfall, install a snow-protection roof (such as a snow hood) if the
unit is installed in a location where snow may build up and fall from the building's roof or other surface onto
the unit. (Install the hood so that the coolant supply opening at the top of the unit can be used.)
(4) Take care that operating noise and exhaust do not disturb neighboring buildings or homes.
In particular, install so that noise-related local environmental standards, if any, are satisfi ed at the border
with a neighboring dwelling.
(5) Electrical noise resulting from this gas heat pump A/C may affect other electrical devices. When installing
and wiring, take care to leave suffi cient space (3 m or more) between the A/C units (indoor and outdoor
units) - or the power cables - and any other units, antennas, signal cables, or power cords of televisions,
radios, stereos, intercoms, computers, word processors, telephones, and similar devices.
(6) Select an installation location so that the length of refrigerant tubing is within the ranges shown in the table
below.
Table 1
Capacity proportion of the indoor units to the outdoor unit
Minimum capacity of indoor units that can be connected
Maximum number of indoor units (systems) that can be connected
Maximum allowable tubing length (L)
Difference between longest and shortest tubing lengths after the
No. 1 branch (fi rst branching point)
Maximum length of each tube branch
Maximum allowable height difference
between indoor and outdoor units
Maximum allowable height difference between indoor units
Maximum length from the fi rst T-tee to the last T-tee
(*1) The minimum length of tubes between outdoor units and indoor units is 7 m.
(*2) If cooling mode is expected to be used when the external temperature is 10°C or below, install so the
maximum length is 30 m.
(*3) Install so that the height difference between indoor units after the fi nal branch is within the limits shown in
the fi gure on the next page.
The grouping of tubes that connect the outdoor units to the indoor units is referred to as the "main tubing."
When the maximum tubing length is more than 90 m (equivalent length), upgrade the tube size 1 rank for
both the liquid and gas tubes of the main tubing.
The prescribed performance cannot be guaranteed if the wrong size is selected.
Over
Over 1 m
2 m
Indoor unit
L1
L2 - L4
ℓ1, ℓ2...ℓ8
If outdoor unit is above
H1
If outdoor unit is below
H2
H3
L3
GB - 24
(Top view)
Over 1 cm
Over
Over
15 cm
1 cm
Over 15 cm
Required distance from fl ammable materials
Fig. 2
45.0kW
56.0kW
50 - 200%
≤ 22 type (equivalent to 0.8 horsepower)
24
≤ 120 m (equivalent length + 145 m)
≤ 30 m
≤ 30 m
≤ 50 m
≤ 35 m
(*2)
≤ 15 m
(*3)
≤ 2 m
(Front view)
Over 60 cm
71.0kW
(*1)

Publicité

Table des Matières
loading

Table des Matières