AM-1 SERIES™
WATER USE FIXTURES
RECIRCULATION
(1)
T
PUMP
AM SERIES
C
M
H
TO DISHWASHER
IF PERMITTED
BY CODES
T
AQUASTAT
WATER
(1) CHECK VALVE
HEATER
Fig. 1. AM-1 Series ASSE 1017 application. Dimensions
shown in in (mm).
Installation of Union Sweat, CPVC,
Union Propress and PEX
Connections
—
Union sweat connections, if used, should be sol-
dered prior to assembly to the valve, or without the
sealing gasket or optional check valve present.
After the joint has cooled, the sealing gasket
and/or check valves may be installed.
—
CPVC fittings are limited to a system maximum
temperature of 180° F (82° C) and 100 psi
(689 kPa).
—
PEX fitting and crimp ring (provided by Installer)
are deigned to meet ASTM F1807 requirements.
—
PEX tubing used with PEX fittings must meet
ASTM F876 requirements.
—
Press connections, use press tools and installation
practices compatible with Viega systems.
Installation of Temperature Gauge
Adapter
IMPORTANT
Union sweat connections must be soldered before
the thermowell with O-ring and sealing gasket are
installed. Install the thermowell with O-ring and
sealing gasket after the joint has cooled.
1. Install thermowell with O-ring to the thermometer
adapter body.
2. Tighten to 75 LB-IN ± 10 LB-IN. DO NOT OVER-
TIGHTEN.
3. Install the thermometer into the thermowell until
seated and tighten the set screw to secure in place.
62-3075EFS—06
All manuals and user guides at all-guides.com
ALLOWABLE
SERVICE
(1)
VALVE
LOCATION
8
HEAT
(203)
COLD
TRAP
MAX
WATER
6
SUPPLY
(152)
V
EXPANSION
TANK
M25029A
SCREW
Fig. 2. Temperature gauge installation.
VALVE ADJUSTMENT
To adjust temperature setting of the mixing valve, attach
thermostrip (supplied with the valve) to the piping
connected to the Mix port of the valve. Loosen handwheel
screw, lift handwheel and turn to desired temperature as
indicated on the thermostrip. Reposition the hand wheel
and retighten screw.
Temperature Setting Procedure
It is possible to limit the temperature range. To use this
feature:
1
2
c
1
LOOSEN SCREW, LIFT HAND WHEEL.
2
TURN HAND WHEEL CLOCKWISE
OR COUNTER CLOCKWISE TO
ADJUST TEMPERATURE.
2
THERMOMETER
THERMOWELL
O-RING
THERMOMETER
ADAPTER WITH
UNION NUT
GASKET
M36644
4
2
3
c
H
3
REPOSITION HAND WHEEL
TO LOCK POSITION.
4
RETIGHTEN SCREW.
3
H
M27487