4. For compressor applications: Leave the jumper between termi-
nals J and R in place.
For boiler applications: Remove the jumper between terminals
J and R.
Fig. 5. Terminal Designations showing the jumper
5. For compressors and boilers: Connect a 24 VAC power source
to the R and C terminals on the ERM.
6. Connect terminals from the ERM to the appropriate terminals
on the compressor/boiler control board.
7
FOR COMPRESSOR:
R
J
Jumper J and R
FOR BOILER:
Remove Jumper
between J and R terminals.
Y
J
R
C
24V CAN COME FROM AIR HANDLER
24
(COMPRESSOR APPLICATION)
VAC
V c.a.
OR EXTERNAL TRANSFORMER
Y2
O/B
Y
C
D
L
T
T
Y2
O/B
L S1 S1
D
T
T
Fig. 6.
S1 S1
MCR35657
M35658
33-00135EFS—11