6 MESSAGES SHOWN ON THE DISPLAY
Mess.
Gate is closed
Gate is open
Opening under way
Closing under way
While in step-by-step mode, the control board awaits further instructions after a START command
Stop command received
CST activated while working in barrier mode
Mess.
They point out that the gate has exceeded:
- (Err1), the max allowed number of reversals (50) wi-
thout ever reaching the end of stroke (or stop) while
closing;
- (Err2) the max number of uninterrupted operations
(10) of the anti-crush safety device;
therefore an "emergency operation" is under way: the
control board sets the motors at a slow speed and sear-
ches the stops (or ends of stroke) in order to reset the
positioning system. Once the stops (or ends of stroke)
while closing are found again the message disappears
and the control board awaits further instructions "- - - -"
and then resumes working normally.
External photocells and/or safety devices are activated
or out of order.
The motors are not connected or signals control board
failure.
Possible motor overheating due to obstacles hindering
the gate/door movement. The control board does not
respond to instructions.
Operators mouvement not detected.
7 INSTALLATION TEST
The testing operation is essential in order to verify the correct installation of the system. DEA System wants to summarize the proper
testing of all the automation in 4 easy steps:
• Make sure that you comply strictly as described in paragraph 2 "WARNINGS SUMMARY";
• Test the opening and closing making sure that the movement of the leaf match as expected. We suggest in this regard to perform va-
rious tests to assess the smoothness of the gate and defects in assembly or adjustment;
• Ensure that all safety devices connected work properly;
• Perform the measurement of impact forces in accordance with the standard 12445 to find the setting that ensures compliance with
the limits set by the standard EN12453.
WARNING With control boards range "RR" disconnect the power supply wires before unlocking the operator manually. When you start
the operator again the first operation will bring the door to a complete closing. If you do not follow this procedure the door will lose its
right positioning.
8 PRODUCT DISPOSAL
WARNING In compliance with EU Directive 2002/96/EC on waste electrical and electronic equipment (WEEE), this electrical prod-
uct should not be treated as municipal mixed waste. Please dispose of the product and bring it to the collection for an appropriate
local municipal recycling.
20
All manuals and user guides at all-guides.com
WORKING STATUS MESSAGES
ERROR MESSAGES
Description
In case the gate is not properly closed after the emergency operation (maybe because
of false stops or obstacles due to mechanical frictions), proceed as follows:
- Disconnect the power supply, check manually that no particular frictions and/or ob-
stacles are present during the complete stroke of the gate/door. Leave the gate/door
half-open.
- Connect the power supply again and subsequently give a start pulse. At this point the
gate/door will start to close at slow speed until reaching the stop (or end of stroke).
Make sure that the gate operation is properly completed. Adjust force and motor speed
values, if needed.
If the gate keeps working improperly repeat the motor stroke memorization procedure.
Make sure that all safety devices and/or photocells installed are working properly.
Make sure that the motors are properly connected. If the message reappears change
the control board.
Remove any obstacle and wait until the message "Err6" is replaced by message "bLOC"
and the control board responds to instructions again (a few seconds).
- Make sure that operators and encoders connections are well done.
- Check the setting of parameter P034 (Motor selection with or without encoder) and
make sure it is correct.
- If this error appears again, replace the control panel.
Description