Maintenance / Cleaning

9.1 Maintenance

To protect the paintwork, avoid leaning anything against the de-
vice or putting objects on the device. External heat pump parts
can be wiped with a damp cloth and domestic cleaner.
NOTE
Never use cleaning agents containing sand, soda, acid or chloride as
these can damage the surfaces.
To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating system
can not be contaminated. We recommend protecting the evapo-
rator by installing a bird guard in the inlet duct. At least 80% of the
cross section of the grating should be open. In the event that op-
erating malfunctions due to contamination still occur, the system
should be cleaned as described below.

9.2 Cleaning the Heating System

The ingress of oxygen into the heating water circuit may result in
the formation of oxidation products (rust), particularly if steel
components are used. These products enter the heating system
via the valves, the circulating pumps and/or plastic pipes. It is
therefore essential - in particular with respect to the piping of un-
derfloor heating systems - that only diffusion-proof materials are
used.
NOTE
We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.
Residue from lubricants and sealants may also contaminate the
heating water.
In the case of severe contamination leading to a reduction in the
performance of the liquifier in the heat pump, the system must be
cleaned by a heating technician.
Based on current knowledge, we recommend carrying out the
cleaning with a 5 % phosphor acid or, if more frequent cleaning
is required, with a 5 % formic acid.
In either case, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction op-
posite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating sys-
tem circuit, we recommend connecting the flushing device di-
rectly to the flow and return flow of the liquifier of the heat pump.
It is important that the system be thoroughly flushed using appro-
priate neutralising agents to prevent any damage from being
caused by cleaning agent residue remaining in the system.
Acids must be used with great care and all relevant regulations of
the employers' liability insurance associations must be adhered
to.
The manufacturer's instructions regarding cleaning agent must
be complied with at all times.
EN-9
All manuals and user guides at all-guides.com

9.3 Cleaning the Air System

Air ducts, evaporator, ventilator and condensate outflow should
be cleaned of contamination (leaves, twigs, etc.) before each
new heating period. Do this by opening the front of the heat
pump. The bottom should be opened first followed by the top.
Before opening the device, ensure that all circuits are isolated from the
power supply.
Remove and rehang the side panel assemblies as described in
Chapter 4.
To prevent the evaporator and the condensate tray from being
damaged, do not use hard or sharp objects for cleaning.
9.4 Maintenance
Devices with a minimum of 3 kg refrigerant, or hermetically
sealed devices with a minimum of 6 kg refrigerant must be leak-
proof tested yearly by the operator according to (EC) No. 842/
2006.
The leak-proof testing is to be documented and archived for a
minimum of 5 years. The test is to be carried out by certified per-
sonnel only according to (EC) No. 1516/2007. The attached table
can be used as a basis for the documentation.
NOTE
Local regulations may differ from EU directive 842/2006. The appropriate
local regulations for heat pump leak tests must be observed.
10 Faults / Trouble-
This heat pump is a quality product and is designed for trouble-
free operation. In the event that a fault should occur, it will be in-
dicated on the heat pump manager display. Simply consult the
Faults and Trouble-shooting page in the operating instructions of
the heat pump manager. If you cannot correct the fault yourself,
please contact your after-sales service technician.
Any work on the heat pump may only be performed by an authorised and
qualified customer service.
11 Decommissioning/
Before removing the heat pump, disconnect it from the power
source and close all valves. The deinstallation of the heat pump
must be performed by technical personnel. Observe all environ-
mentally-relevant requirements regarding the recovery, recycling
and disposal of materials and components in accordance with all
applicable standards. Particular attention should be paid to the
proper disposal of refrigerants and refrigeration oils.