fafnir TORRIX Documentation Technique page 33

Le capteur de niveau magnétostrictif
Table des Matières

Publicité

rUVNORD
Schedule to EU-Type Examination Certificate No. TÜV 99 ATEX 1496 X issue 02
Type VISY-Stick ■■■ TLS
Temperature dass
Ambient temperature ränge
Medium temperature ränge
T4
-40 °C to +75 °C
-40 °C to +135 °C
T3
-40 °C to +85 °C
-40 °C to +200 °C
T2
-40 °C to +85 °C
-40 °C to +300 °C
T1
-40 °C to +85 °C
-40 °C to +450 °C
Use as category 1D apparatus
Type TQRRIX Ex
__________
Maximum surfa
Dust layer < 5 mm
ce temperature
Immersed in dust
Ambient temperature Ta
Ta + 75 °C
Observe EN 60079-14
-40 °C to +85 °C
Type VISY-Stick
resp. TORRIX Ex SC.
Maximum surfa
Dust layer < 5 mm
ce temperature
Immersed in dust
Ambient temperature Ta
Ta + 30 °C
135 °C
-40 °C to +85 °C
Type VISY-Stick ... TLS
Maximum surfa
Dust layer < 5 mm
ce temperature
Immersed in dust
Ambient temperature Ta
135 °C
135 °C
-40 °C to +77 °C
Ta + 110 °C
Observe EN 60079-14
-40 °C to +85 °C
Type VISY-Stick
RS485 resp. TORRIX Ex C... resp. TORRIX Ex RS485... resp. TORRIX Ex TAG..
Maximum surfa
Dust layer < 5 mm
ce temperature
Immersed in dust
Ambient temperature Ta
li<100 mA: Ta + 40 °C
Observe EN 60079-14
-40 °C to +85 °C
li < 200 mA: Ta + 55 °C
Observe EN 60079-14
-40 °C to +70 °C
All further data are valid unchanged.
(16)
Drawings and documents are listed in the ATEX Assessment Report No. 20 203 254816
(17)
Specific Conditions for Use
1. When using Titanium Floats or Sump Environmental Sensors, the risk of ignition due to impact or
friction shall be avoided.
2. When using plastic floats, there is a danger of ignition due to electrostatic discharge. The
manufacturer's instructions must be observed.
(18)
Essential Health and Safety Requirements
no additional ones
- End of Certificate -