6. Electrical work
<Example of "F2" calculation>
*Condition PEFY-NMSU × 4 + PEFY-NMAU × 1, C = 8 (refer to right sample chart)
F2 = 18.6 × 4/8 + 38 × 1/8
= 14.05
→ 16A breaker (Tripping current = 8 × 16A at 0.01s)
*3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type1) + V2 × (Quantity of Type2) + V2 × (Quantity of Type3) + V2 × (Quantity of Others)
+ V3 × (Wire length[km])
G1
Current sensitivity
30 or less
30 mA 0.1sec or less
100 or less
100 mA 0.1sec or less
Wire thickness (mm
2
/AWG)
2.1/14
3.3/12
5.3/10
M1 M2
M1 M2
S
1
2
TB3
TB5
Fig. 6-3
M1 M2
M1 M2
TB3
TB5
Fig. 6-4
8
V3
48
56
66
M1 M2
S
1
2
TB15 TB5
TB15
S
M1 M2
S
TB5
6.3. Connecting remote controller, indoor and outdoor
transmission cables
• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The "S" on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.
• Install a remote controller following the manual supplied with the remote controller.
• Connect the remote controller's transmission cable within 33 ft. (10 m) using a 0.75
2
mm
(AWG18) core cable. If the distance is more than 33 ft. (10 m), use a 1.25
mm
2
(AWG16) junction cable.
1 MA Remote controller (Fig. 6-3)
• Connect the "1" and "2" on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)
• DC 9 to 13 V between 1 and 2 (MA remote controller)
2 M-NET Remote controller (Fig. 6-4)
• Connect the "M1" and "M2" on indoor unit TB5 to a M-NET remote controller.
(Nonpolarized 2-wire)
• DC 24 to 30 V between M1 and M2 (M-NET remote controller)
3 Wireless remote controller (When installing wireless signal receiver) (Fig. 6-5)
• Connect the wire of wireless signal receiver (9-pole cable) to CN90 of indoor con-
troller board.
• When more than two units are run under group control using wireless remote
controller, connect TB15 each with the same number.
• To change Pair No. setting, refer to installation manual attached to wireless re-
mote controller. (In initial setting of indoor unit and wireless remote controller, Pair
No. is 0.)
Terminal block for indoor transmission cable
A
Terminal block for outdoor transmission cable
B
M1(A), M2(B),
(S)
;
Remote controller
C
CN90
M1 M2
Pair No.
M1 M2
S
0
TB3
TB5
9
Pair No.
0
Fig. 6-5
Sample chart
6000
600
SAMPLE
60
10
1
0.1
0.01
1
2
3
4
6
8
10
C
Rated Tripping current (x)
Wireless signal receiver
D
Wireless remote controller
E
CN90
1
2
Pair No.
M1 M2
S
1
2
0
TB15
TB5
9
20
TB15