. Installation location

W
Fig. 2-1

3. Installing the indoor unit

1
2
4
6
Fig. 3-1
A
1/16
B
2-15/16
9-3/16
9-11/16
Fig. 3-2
7-1/2
3-1/8
Ø2-9/16
Fig. 3-3
(inch)
9-5/16
Min. 19-11/16
3
5
7
(inch)
9-5/16
1/16
3-3/8
3-3/8 1/16
5-7/16
C
D
9-3/16
9-11/16
2-3/4
6-5/16
4-15/16
Ø3-15/16
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and main-
tenance.
(inch)
Models
W
P15
37-13/16
P24
50-3/8
P30, P36
63
Warning:
Mount the indoor unit on a ceiling strong enough to withstand the weight of the unit.
2.2. Outline dimensions (Outdoor unit)
Refer to the outdoor unit installation manual.
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories
(contained in the inside of the intake grille).
Accessory name
Washer
4 pcs
1
Pipe cover
1 pc Large size (For gas tubing)
2
Pipe cover
1 pc Small size (For liquid tubing)
3
Band
4 pcs
4
Joint socket
1 pc Marked with "UNIT"
5
Socket cover
1 pc
6
Drain tubing cover
1 pc
7
3.2. Preparation for installation (Fig. 3-2)
3.2.1. Suspension bolt installing spacing
(inch)
Models
A
B
P15
36-1/8
37-13/16
P24
48-11/16
50-3/8
P30,36
61-5/16
63
3.2.2. Refrigerant and drain tubing location
(inch)
Models
C
D
P15
7-1/4
P24,P30,P36
7-1/16
7-7/8
A Front side outlet
B Left side outlet
C Right side outlet
D Independent piece (Removable)
E Right drain tubing
3.2.3. Selection of suspension bolts and tubing positions (Fig. 3-3)
Caution:
Install the indoor unit at least 8 ft. (2.4 m) above floor or grade level. These
appliances are not accessible to the general public.
Using the pattern paper provided for installation, select proper positions for suspen-
sion bolts and tubing and prepare relative holes.
A Pattern paper
B Suspension bolt hole
C Indoor unit width
Secure the suspension bolts or use angle stock braces or square timbers for bolt
installation.
D Use inserts of 220-230 lbs. each.
E Use suspension bolts of W 3/8 or M10 in size.
Q'ty
8
F Left drain tubing
G Gas tubing
H Liquid tubing
I Rubber plug
J with Joint socket 5
3