Requires firmware version B.03.02.1232 and up for models RP793xA and RP794xA.
l
When units are paralleledd, the programmable output resistance is reduced. The programmable
l
output resistance for a single unit must be divided by the total number of paralleled units.
[SOURce:]VOLTage:RESistance:STATe 0|OFF|1|ON
[SOURce:]VOLTage:RESistance:STATe?
Enables or disables output resistance programming. Only applies in voltage priority mode.
Parameter
0|OFF|1|ON, *RST OFF
Turns resistance programming on: VOLT:RES:STAT ON
Requires firmware version B.03.02.1232 and up for models RP793xA and RP794xA.
l
[SOURce:]VOLTage:SLEW[:IMMediate] <value>|MIN|MAX|INFinity
[SOURce:]VOLTage:SLEW[:IMMediate]? [MIN|MAX]
Sets the voltage slew rate. The slew rate is set in volts per second and affects all programmed
voltage changes, including those due to the output state turning on or off. The slew rate can be set to
any value between 0 and 9.9E+37. For very large values, the slew rate will be limited by the unit's
listed programming speed and bandwidth. The keywords MAX or INFinity set the slew rate to
maximum.
Parameter
0 – 9.9E+37, *RST MAX
Sets the output slew rate to 5 V per second: VOLT:SLEW 5
The query returns the value that was sent. If the value is less than the minimum slew rate, the min-
l
imum value is returned. The slew setting resolution is the same as the minimum value, which can
be queried using VOLTage:SLEW? MIN. The exact value varies slightly according to calibration.
[SOURce:]VOLTage:SLEW:MAXimum 0|OFF|1|ON
[SOURce:]VOLTage:SLEW:MAXimum?
Enables or disables the maximum slew rate override.  When enabled, the slew rate is set to its
maximum value. When disabled, the slew rate is set to the immediate value set by the VOLTage:SLEW
command. Use VOLTage:SLEW? MAX to query the maximum slew rate that was set.
Parameter
0|OFF|1|ON, *RST ON
Enable the maximum slew rate override: VOLT:SLEW:MAX ON
The VOLTage:SLEW:MAX command is coupled to the VOLTage:SLEW command. If
l
VOLTage:SLEW sets the rate to MAX or INFinity, VOLTage:SLEW:MAX is enabled. If the slew rate
is set to any other value, VOLTage:SLEW:MAX is disabled.
Keysight RP7900 Series Operating and Service Guide
5 SCPI Programming Reference
Typical Return
0 or 1
Typical Return
<max value>
Typical Return
0 or 1