3.4 Troubleshooting

Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the display lights up indicating
the fault code and, in case of cascade connection, the module number.
There are faults that cause permanent shutdowns which can be reset by pressing the OK button for one second or
with the RESET button on the remote timer control (optional) if installed. If the boiler fails to restart after resetting, it
is necessary to eliminate the fault first.
Other faults cause temporary shutdowns which are automatically reset as soon as the value returns within the
boiler's normal working range.
Table of faults
Table 8- List of faults
Fault
Fault
code
01
No burner ignition
Flame present signal
02
with burner off
Overtemperature pro-
03
tection intervention
Fume extraction duct
04
safety device interven-
tion
Fan protection interven-
05
tion
No flame after ignition
06
phase (6 times in 4
minutes)
07
High fume temperature
Heating sensor 1 (flow)
overtemperature indica-
08
tion
(Viewable only in His-
tory Menu)
Return sensor overtem-
perature indication
09
(Viewable only in His-
tory Menu)
Heating sensor 1 (flow)
10
fault
EN
Possible cause
No gas
Ignition/detection electrode fault
Faulty gas valve
Insufficient gas supply pressure
Trap blocked
Electrode fault
Card fault
No water circulation in the system
Air in the system
Fault 07 generated 3 times in the last 24 hours
Fault 15 generated for 1 hour consecutive
Ionization electrode fault
Flame unstable
Gas valve Offset fault
air/fume ducts obstructed
Trap blocked
Exchanger dirty
Exchanger deteriorated
Sensor does not indicate the correct temperature
insufficient system water circulation
insufficient system water circulation
Sensor damaged
Wiring shorted
Wiring disconnected
cod. 3541V233 - Rev 00 - 06/2022
Cure
Check the regular gas flow to the boiler and that
the air has been eliminated from the pipes
Check the wiring of the electrode and that it is
correctly positioned and free of any deposits
Check the gas valve and replace it if necessary
Check the gas supply pressure
Check the trap and clean it if necessary
Check the ionization electrode wiring
Check the card
Check the circulating pump
Vent the system
See fault 07
See fault 15
Check the position of the ionization electrode and
replace it if necessary
Check the burner
Check the Offset adjustment at minimum power
Remove the obstruction from the flue, fume
extraction ducts, air inlet and terminals
Check the trap and clean it if necessary
Clean the exchanger
Check the integrity of exchanger
Check the fume sensor or replace it
check water circulation
check water circulation
Check the wiring or replace the sensor