Examples
Double subbases used
Example 1
Double subbases for double solenoid valves
Example 2
Double subbases for double solenoid valves
Example 3
Double subbases for double solenoid valves
Example 4
Double subbases for single solenoid valves
Example 5
Double subbases for double solenoid valves
Combined with
Double subbases for single solenoid valves
Example 6
Double subbases for double solenoid valves
Combined with
Double subbases for single solenoid valves
1)
These examples only apply if there are no module extensions. Other combinations may be selected in accordance with
your requirements.
2)
From an electrical connection viewpoint, the subbases for double solenoid valves must come first and then those for
single solenoid valves.
The maximum number of solenoids for all subbases is 32.
AVENTICS | PROFINET-IO | R412015162–BDL–001–AE
Voltage at switches
Switches can be damaged if voltage is applied during
operation.
O
Always operate switches in a voltage-free state!
How to assign the valve supply:
1. Open the lower screw cap B (see Fig. 6 on page 88).
2. Using the S4, S5, S6, and S7 switches, assign each valve
group to one of the two supply voltages U
(see Fig. 6 and Table 16 on page 88).
Below you will find examples for the assignment of the S4, S5,
S6, and S7 switches and for supplying assembled valves in
Table 17 on page 90 (examples 1 to 3) and Table 18 on page 91
(examples 4 to 6). The following example combinations are
listed there:
2)
Commissioning and Operation
NOTICE
Q1
Valve equipment
Double solenoid valves
Single solenoid valves
Single and double solenoid valves
Single solenoid valves
Double solenoid valves
Single solenoid valves
Single and double solenoid valves
Single solenoid valves
89
or U
Q2

Publicité