G 35 gas
LANDIS 8 GYR ARC 466890660
FOR SUPPLY 220 V TWO-PHASE
WIRING DIAGRAMS
The installer has to effect the following connections:
• supply line
• thermostatic line
• eventual blocking lamp
• eventual hour-meter
• eventual flame modulation thermostat
(remove the supporting cable)
N.B. It is necessary to follow the rule that indicates the
connection of no more than two cables for each terminal.
Warning:
• do not exchange the neutral with the phase
• make the connection to an efficient earthing system
• respect the regulations in force
The supply line has to reach the burner by a 15 A main switch and be
protected by 10 A fuses.
The connecting cables shall have a section not inferior to 1,5 mm
insulation of 2000 volts.
Connect has shown in the enclosed wiring diagram.
Make the connection to an efficient earthing system.
The earth connection to the terminal board of the burner must be made with
a cable at least 20 mm longer than the phase and neutral cables.
BLACK
BROWN
0
223344
2
RED
ORANGE
1
2
3
1
Automatic control devices
2
7 pole connector
3
6 pole connector
4
Control solenoid valve
5
Gas adjustment solenoid valve
6
Ambient temperature thermostat
7
Ignition transformer
8
Noise filter
9
Time switch
10
Main line fuses
11
Auxiliary circuit fuse
12
Main switch
13
All-on all-off switch
14
Flame control
and an
15
Remote indication lamp – locked burner
16
Boiler temperature thermostat
17
Multiblock double valve
18
Fan motor
19
Air pressure switch
20
Minimum gas pressure switch
YELLOW GREEN BLUE VIOLET
4
5
6
7
SEAL CONTROL DUNGS
TYPE VPS 504 SERIES 02
GREY
WHITE
EARTH NEUTRAL PHASE
8
9
T
pag. 47
N
Ph