Troubleshooting

Safety

Risk of electric shock.
This can result in serious injuries or death.
Danger from an inadequate ground conductor connection.
This can result in severe personal injury or damage to property.
Protective
equipment
82
WARNING!
Before opening the device:
Unplug the device from the mains.
Disconnect battery.
Put up an easy-to-understand warning sign to stop anybody inadvertently
switching it back on again.
Using a suitable measuring instrument, ensure that electrically charged com-
ponents (e.g. capacitors) have been discharged.
WARNING!
The housing screws provide a suitable PE conductor connection for earthing
the housing and must NOT be replaced by any other screws that do not pro-
vide a reliable PE conductor connection.
Charger leads connected to wrong po-
les, reverse polarity protection has
tripped
Remedy:
-
Connect battery poles correctly
Short circuit in the charging terminals
or charger lead, short-circuit detection
active
Remedy:
-
Check charger leads, contacts and
battery poles
Mains fault - mains voltage outside the
tolerance range
Remedy:
-
Check mains conditions