3 Consult with a specialist about water quality control methods and
calculations before using anti-corrosive solutions.
4 When replacing a previously installed air conditioning device (even when
analysis and check for possible corrosion.
Corrosion can occur in cold-water systems even if there has been no
prior signs of corrosion.
replacing the unit.

8.4. Pump interlock

The heat source unit may become damaged if it is operated with no water
circulating through the pipes.
Interlock unit operation and the water-circuit pump. Use the terminal
In the case of a pump interlock circuit signal connection to the TB8-3, 4, remove
the short-circuit wire. Also, use pressure valve 63PW with a minimum current of
5mA or less to prevent miss detection due to poor connection.
Pump interlock cords of parts of appliances for heat source use shall not be

9. Refrigerant piping installation

The pipe is connected via a terminal-branch type connection in which refrigerant
piping from the heat source unit is branched at the terminal and is connected to
each of the indoor units.
connection. Note that the branched sections are brazed.
Warning:
Do not use refrigerant other than the type indicated in the manuals
provided with the unit and on the nameplate.
during use, during repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible
for malfunctions or accidents resulting from the use of the wrong type of
refrigerant.
Always use extreme care to prevent the refrigerant gas from leaking while
from any source, such as a gas stove, it breaks down and generates
a poisonous gas which can cause gas poisoning. Never weld in an
unventilated room. Always conduct an inspection for gas leakage after
installation of the refrigerant piping has been completed.

9.1. Caution

This unit uses refrigerant R410A. Follow the local regulations on materials and
pipe thickness when selecting pipes.
1 Use the following materials for refrigeration piping.
Material: Use copper alloy seamless pipes made of phosphorus
deoxidized copper. Ensure the inside and outside surfaces of
the pipes are clean and free from hazardous sulfur, oxide, dusts,
Size: Refer to item 9.2. for detailed information on refrigerant piping
system.
2 Field-supplied piping often contains dust and other materials. Always blow it
clean with a dry inert gas.
3 Use care to prevent dust, water or other contaminants from entering the
piping during installation.
4 Reduce the number of bending portions as much as possible, and make
bending radii as big as possible.
5 For branching and connecting pipes for indoor and heat source units, use
Indoor twinning pipe kit model
Line branch
Down-stream unit model
Less than 30 in total
CMY-Y102SS-G2
Heat source twinning kit model
Total heat source model
P144 ~ P240
CMY-Q100CBK2
Total indoor model
P72~P96
CMY-R160C-J
Total heat source model
P288 ~ P336
CMY-Q200CBK
[Fig. 8.4.1] (P.3)
A
[Fig. 8.4.2] (P.3)
This circuit is for interlocking of the heat source unit operation and the water-
circuit pump.
A
Heat source unit
C
To next heat source unit
X
: Relay
FS
: Flow switch
52P
: Magnetic contactor for water circuit pump
MP
: Water circuit pump
MCB
: Circuit breaker
* Remove the short circuit wire between 3 and 4 when wiring to TB8.
* Use an insulated ring terminal to connect the wiring to TB8.
Copper pipe size and radial thickness for R410A CITY MULTI.
Radial thickness Radial thickness
ø6.35
ø1/4"
0.8
ø9.52
ø3/8"
0.8
ø12.7
ø1/2"
0.8
ø15.88
ø5/8"
1.0
*ø19.05
ø3/4"
1.2
*ø19.05
ø3/4"
1.0
ø22.2
ø7/8"
1.0
ø25.4
ø1"
1.0
ø28.58
ø1-1/8"
1.0
ø31.75
ø1-1/4"
1.1
ø34.93
ø1-3/8"
1.2
ø41.28
ø1-5/8"
1.4
conditioner.
6
of a branching pipe.
7 Follow the restrictions on the refrigerant piping (such as rated length, height
heating/cooling performance.
Line branch
Down-stream unit
Down-stream unit
model
model
More than 73 and
Less than 72 in
less than 144 in
total
total
CMY-Y102SS-G2
CMY-Y102LS-G2
Indoor twinning pipe set model
Header branch
4 branching
8 branching
CMY-Y104C-G
CMY-Y108C-G
Heat source twinning kit model
Total heat source model
Total heat source model
P144 ~ P240
CMY-Y100CBK3
CMY-Y200CBK2
8 Indoor units cannot be further branched down stream after the branch
To the heat source unit
To the heat source
unit
B
Pipe type
32
Type-O
32
Type-O
32
Type-O
40
Type-O
48
Type-O
40
Type-1/2H or H
40
Type-1/2H or H
40
Type-1/2H or H
40
Type-1/2H or H
44
Type-1/2H or H
48
Type-1/2H or H
56
Type-1/2H or H
Down-stream unit
Down-stream unit
model
model
More than 145
More than 241 in
and less than 240
total
in total
CMY-Y202S-G2
CMY-Y302S-G2
10 branching
CMY-Y1010C-G
P288 ~ P360
CAP
25