If "Master" is selected, the detector can be programmed to
function with one or more additional detectors as "Slaves".
A Slave detector can also be set up to only detect the light level
where this is desired.
Depending on the function selected, it will be possible to
program associated objects in order to achieve correct lighting
control.
Confi guration:
It is possible to choose between three methods when confi guring
the detector. This guide describes "Basic" and "Optimisation".
Basic:
In Basic, the detector can be confi gured in just a few moments.
You need only select a few parameters, and the detector will be
ready for use.
It is possible to choose between these functions: Stand-Alone –
Master – Slave.
Then select application: Corridor/stairwell, Offi ce/conference
room, Exhibition hall, Educational or training premises or
Production facility.
In addition, select the number of daylight zones: 1, 2 or 3. Finally,
make a selection as to whether an extra manual zone is installed,
e.g. for pendant or blackboard lighting.
Optimisation:
In Optimisation, these parameters can be selected:
Desired light level at working level – Factory setting: 300 lux
Connection and disconnection of control via IR remote 41-930
(accessory) – Factory setting: On
Feedback via the built-in LED's – Factory setting: On
Calibration of the lighting system – Factory setting: Off
Walk test, test of the detection range – Factory setting: Off
Hysteresis of the built-in light sensor –
Factory setting: 10%.
Basic or advanced confi guration – Factory setting: Basic
Confi guration of delay – Factory setting: 10 min.
Division of detection range into sectors –
Factory setting: 360°
Activation/deactivation of presence detection –
Factory setting: On
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | info@servodan.dk | www.servodan.com
Confi guration of orientation light – Factory setting: Off
Confi guration of burn-in time – Factory setting: 100 hours
Sensitivity – Factory setting: 100%
Additional information and explanations are available on
www.servodan.dk
Advanced:
All parameters and objects are listed here, and can be
programmed as needed/desired.
Guide to advanced confi guration, and sample scenarios of
programming and settings.
See www.servodan.dk, where you can also download the
parameter database.
Screenshot examples:
Calibration:
The lighting system may be calibrated in one of two different
ways: Either automatically or manually. For automatic
calibration, specify the desired lux level at working level in Basic
confi guration. A lux meter is used to measure lighting intensity
at working level. This value is entered in the parameter window
"Desk/sensor Daylight Proportion".
Settings:
Local settings of the desired light level and latency can be
changed using IR remote 41-930 (accessory).
GB
8(22)