Technical data
Operating voltage [V] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 ... 30 DC
Current consumption [mA] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 65
Current rating [mA] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 x 250
Short-circuit prot., reverse polarity prot. / overload prot., watchdog
Voltage drop [V]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 2
Power-on delay time [s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.2
Min. response time switching outputs [ms] . . . . . . . . . . . . . . . . . . . . . . 3*)
Switching frequency [Hz] . . . . . . . . . . . . . . . . . . . . . . . . . . 170 ... 0.125**)
Analogue output. . . . . . . . . . . . . . . . . . . . . . . . . . . 4 ... 20 mA / 0 ... 10 V
Max. load current output [Ω] . . . . . . . . . . . (U
Min. load with voltage output [Ω] . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000
Min. response time analogue output [ms]. . . . . . . . . . . . . . . . . . . . . . . . . 3
Accuracy / deviations (in% of the span)
- Accuracy of switch point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ± 0.5
- Characteristics deviation (linearity, incl. hysteresis and
3)
repeatability
- Linearity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ± 0.5
- Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ± 0.1
- Repeatability (with temperature fluctuations < 10K) . . . . . . . . . . . . < ± 0.1
- Long-time stability (in% of the span per year) . . . . . . . . . . . . . . . . < ± 0.1
- Temperature coefficients (TEMPCO) in the compensated
temperature range 0 ... +80°C (in% of the span per 10 K)
- greatest TEMPCO of the zero point / of the span . . . . . . < ± 0.1 / < ± 0.2
Materials (wetted parts) . . . . . stainless steel (303S22); ceramics; FPM (Viton)
Housing material . . . . . . . .stainless steel (304S15); stainless steel (316S12);
Protection PN2020 - PN2022 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 67 III
Protection PN2023 - PN2027, PN2009, PN2069 . . . . . . . . . . . . . . . IP 65 III
Insulation resistance [MΩ] . . . . . . . . . . . . . . . . . . . . . . . . > 100 (500 V DC)
Shock resistance [g] . . . . . . . . . . . . . . . . . . . . 50 (DIN / IEC 68-2-27, 11ms)
Vibration resistance [g] . . . . . . . . . . . . . 20 (DIN / IEC 68-2-6, 10 - 2000 Hz)
Switching cycles min. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 million
Operating temperature / storage temperature [°C] . . -25 ... +80 / -40 ... +100
Medium temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80
EMC
EN 61000-4-2 ESD: . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EN 61000-4-3 HF radiated: . . . . . . . . . . . . . . . . . . . . . . . . . 10 V/m
EN 61000-4-4 Burst: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 KV
EN 61000-4-5 Surge: . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 / 1 KV
EN 61000-4-6 HF conducted: . . . . . . . . . . . . . . . . . . . . . . . . 10 V
1)
to EN50178, SELV, PELV; referring to UL: see page 22 (Electr. connection).
2)
all indications are referred to a turn down of 1:1
3)
limit value setting to DIN 16086
*) 6 (PN2069) **) max. 90 (PN2069)
30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ± 0.6
PC(Macrolon); Pocan; PEI; EPDM/X (Santoprene); FPM (Viton)
in addition PTFE (PN2023 - PN2027, PN2009, PN2069)
- 10) x 50; 700 at U
B
2)
1)
= 24V
B
4 / 8 KV