Technical data

General data and operating conditions

4
Technical data
4.1
General data and operating conditions
General data
Protection of persons and device protection
Enclosure
Insulation
resistance
Operating conditions
Ambient conditions
Climatic
Storage
Transport
Operation
Permissible
humidity
Pollution
Site altitude
Mechanical
Vibration
resistance
Electrical
Mains connection
Power system
TT, TN
(with
earthed
neutral)
IT
34
EN 60529
NEMA 250
EN 61800-5-1
IEC/EN 60721-3-1
IEC/EN 60721-3-2
IEC/EN 60721-3-3
EN 61800-2
EN 61800-5-1
EN 61800-5-1
Germanischer Lloyd,
general conditions
IP20
Not in the wire range
of the terminals
IP21
With additional cover
Protection against
accidental contact
according to type 1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
1K3 (-25 ... +55 °C)
2K3 (-25 ... +70 °C)
3K3 (-10 ... +55 °C)
Humidity class 3K3 (without condensation;
average relative humidity 85 %)
Degree of pollution 2
< 4000 m amsl
Above 1000 m amsl reduce the power by
5 %/ 1000 m.
Acceleration resistant up to 1 g
Operation is permitted without any restrictions.
Max. mains voltage 400 V!
Observe instructions for special measures!