10
Technical Data
10.1
General
Voltage supply to main
board:
Control function:
Conductivity
measurement:
Measurement range:
Precision:
Reproducibility:
Real-time clock:
Inputs:
Outputs:
Protection class
Protection class:
Environmental
temperature
Dimensions:
Weight
We must reserve the right to make technical modifications as our products are subject to
continuous development.
417101555_CoolProtect.doc
230 V AC, 15 VA 50/60 Hz
Conductivity regulator
Time control
0 - 3000 uS/cm in steps of 1 uS/cm
±
Amplitude variation max. ± 2.5% of the set value
with battery buffering (lifespan > 10 years)
On the main board:
− Voltage supply 2 x 12 VAC
− Conductivity sensor, inductive
− Temperature sensor for conductivity
− Release contact, 5 VAC
On the relay board:
− Alternator contact for alarm(s)
− Acoustic alarm, 24 VAC (buzzer)
− Alternator contact for bleeding
− Alternator contact for Biocide control
IP 65
III
Max. 45°C
360 x 110 x 160 mm (W x D x H)
Approx. 4.8 kg
- 73 -
Rev.: 08-06/10