8.2.4
Connector assignments of Slot VIII (5-terminal)
input for pulse, standard signal input and metering lock
Fig. 8.11 Connector assignments of Slot VIII (5-terminal), input for pulse, standard signal and metering lock
Remove the protective cap
Mount the connector plug according to the connector assignment.
WARNING
Only use a connector plug from our product range!
8.2.4.1
Installing the pulse control (water meter)
8.2.4.2
Installing the standard signal (mA)
8.2.4.3
Installing the metering lock
The metering lock function must be activated in menu first. (see chapter:
NOTE
"configuration / metering lock") The metering lock is available in all operation modes.
Fig. 8.14 Installing the metering lock
417101438_EMP_II_E60
Conductor coloring
Pin
(cable connection)
1
brown
2
white
3
blue
4
black
5
grey
Assignment
Output 5 V, DC (load with max. 50 mA)
Input external pulse
Input metering lock
GND (┴)
Input standard signal 0/4-20 mA
2
+
4
= Pulse input with potential-free contact
PIN
Assignment
2
Relay input
4
GND (┴)
1
+
2
+
4
= Pulse input with electronic switch (NPN)
PIN
Assignment
1
5 V, DC
2
Relay input
4
GND (┴)
The minimum pulse- or pause time is 15 ms.
Fig. 8.12 Installing the pulse control (water meter)
4
+
5
= Standard signal input 0/4 – 20 mA
PIN
Assignment
4
0/4-20 mA (-)
5
0/4-20 mA (+)
Fig. 8.13 Installing the standard signal (mA)
WARNING
3
+
4
= Metering lock input with potential-free
contact
PIN
Assignment
3
Relay input
4
GND (┴)
1 +3
+
4
= Metering lock input with electronic switch
(NPN)
PIN
Assignment
1
5 V, DC
3
Relay input
4
GND (┴)
- 96 -
Observe correct polarity
during connection!