10.3.14.4 MicroFlow
The "Deviation" option is used to specify the number of undetected strokes permitted during
the stroke interval to be monitored (see chapter
the metering monitoring function issues an alarm.
10.3.14.5
MicroFlow
When handling media with a tendency to emit gas, gas bubbles form in the system after
extended downtimes, resulting in corrupted volume values of the quantity to be metered and
subsequently to the non-detection of the metering strokes by the
issuance of an alarm.
417101438_EMP_II_E60
/ Deviation
PLUS
PLUS
/ Metering break
10.3.14.3
"MicroFlow
Fig. 10.43 Configuration MicroFlow
Example: Strokes 40, deviation 20
This example accepts 20
undetected strokes in an interval
of 40 strokes. An alarm is issued if
21 strokes are undetected.
Setting range: 0-100
Default setting = 40
Fig. 10.44 Configuration MicroFlow
"Metering break" is used to set the
period without metering after which
the monitoring system is
deactivated for a specific time (see
chapter
Metering delay") to prevent the
undesired activation of the
monitoring system.
Setting range: 2 - 3600s
Default setting = 240 sec.
- 115 -
PLUS
/ Strokes") before
PLUS
/ Deviation
MicroFlow
and the
PLUS
PLUS
/ Metering break
10.3.14.6
"MicroFlow
PLUS