Manual BVS 20 ATEX E 091 X
Signal lamps
LEDs
24 V DC
100*–230 V AC
*with reduced brightness
Terminal cross
section
2 x 0.75 mm² single colour
3 x 0.75 mm² two-colour
Numerical display
Rated voltage
Terminal cross section
3.4.2 Group IIB+H
2
Illuminated pushbuttons
Electrical data
250 V AC 1,5 A AC-21
24 V DC
LEDs
24 V DC
Terminal cross
section
5 x 0.75 mm² single colour
6 x 0.75 mm² two-colour
3.5
Permissible ambient temperatures
The explosionproof control and signalling
devices, series C22 , have been designed for an
ambient temperature of –20 °C to 40 °C (stan-
dard) or –20 °C to 60 °C (on request).
4.
Installation
The generally recognized rules of engineer-
ing, IEC 60079-14 'Electrical installations
design, selection and erection', national reg-
ulations and the instructions set out in this
manual apply for the installation and opera-
tion.
Control and signalling devices of the series
C22 must not be built into the walls of flame-
proof enclosures.
4.1
Double insulation
With the exception of the rotary switches, all the
devices are doubly insulated and do not have a
connection for a PE conductor.
NOTE! The rotary switch has a PE conductor
and must be connected correctly!
Edition December 2020
Copyright
24 V DC
9 x 0.75 mm²
1.5 A DC-21
thuba Ltd., CH-4002 Basel
Switzerland