Switch the power on and make sure that the status of the LEDs (see fig. 1) is as follows:
- LD1
Red security LED blocking button "TB"
- LD2
Red security LED inverting photoelectric cell "FTCI"
- LD3
Red security LED stop photoelectric cell "FTCS"
- LD4
Red LED closing travel limit 1 activated "FCC1"
- LD5
Red LED opening travel limit 1 activated "FCA1"
- LD6
Red LED closing travel limit 2 activated "FCC2"
- LD7
Red LED opening travel limit 2 activated "FCA2"
- LD8
Red indicator LED manual operation
- LD9
Red indicator LED opening button activated "TA"
- LD10 Red indicator LED closing button activated "TC"
- LD11 Green power on LED
*The LEDs are "on" if the relative security device is inactive (depends on the position of the gate).
Check that the activation of the safety devices (those which have not been bridged or excluded during
programming) switch the corresponding LEDs off.
If the green power on LED doesn't light up check the condition of the fuses and the power cable
connection between binding posts 37 and 38 (fig. 1).
If none of the red LEDs light up check the condition of the fuses and contacts on the terminal board.
If one or more of the safety LEDs do not light up check the contacts of the relative security devices
and check that the unused safety device contacts have been bridged.
INDICATIONS ON THE DISPLAY (DS1)
alarm caused by two travel limits on the same gate leaf being activated together
memorised parameter error
time programming mode block (caused by: TB, FTCI, FTCS)
defining the system configuration
waiting period between system configuration and successive programming stages
torque setting (value 1)
work time programming
opening stage
block
reclosing pause (only if enabled)
closing stage
15
on
on
on
on*
on*
on*
on*
off
off
off
on