Carrier AQUASNAP 30RA Manuel D'installation page 4

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 32
30RA
Physical data and electrical data - Model RA
Table I: Physical data - Model RA
30RA
Net cooling capacity*
Operating weight
without hydronic module
with hydronic module
Refrigerant charge R-407C
Compressor
Evaporator
Net water volume
Water connections (MPT gas)
Maximum water pressure
(unit without hydronic module)
Hydronic module
Pump
Available pressure**
Water inlet connection (MPT gas)
Water outlet connection (MPT gas)
Closed expansion tank water volume
Water fill system (option)
Inlet/outlet diameter (MPT gas)
Condenser
Tube diameter
No. of rows
Tubes/row
Fin spacing
Fan
Diameter
No. of blades
Air flow (high speed)
Fan speed (high speed)
* The ratings indicated refer to an evaporator entering/leaving temperature of 12/7 °C,and air entering the condenser at 35 °C.
** At nominal water flow rate.
Table II: Electrical data - Model RA
30RA
Power supply
Voltage range
Nominal power input*
Effective power input**
Nominal current drawn*
Effective current drawn**
Maximum power drawn***
Maximum current drawn**
Starting current
Pump power input
*
Based on an outdoor entering air temperature of 35 °C db,an evaporator entering water temperature of 12 °C and an evaporator leaving water temperature of 7 °C,unit without hydronic
module
**
The power and current values indicated refer to Eurovent Standard conditions.
*** The power and current values indicated refer to an evaporator leaving water temperature of 10 °C and condenser entering air temperature of 46 °C.
GB - 2
017
kW
17.70
kg
200
kg
220
kg
4.80
One scroll compressor
One plate heat exchanger
l
1.50
inches
1
kPa
1000
Pump, mesh filter, expansion tank, flow switch, pressure gauges, automatic air purge valve and drain plug,
flow control valve and safety valve.
One single-speed pump
kPa
138
inches
1-1/4
inches
1
l
8
inches
1/2
One, copper tubes and aluminium fins
inches
3/8
2
52
mm
1.81
Two,axial type with two speeds
mm
500
5
l/s
2450
r/s
12.83
017
V-ph-Hz
400-3-50 / 400-3-50+N
V
360-440
kW
6.43
kW
6.54
A
10.75
A
10.95
kW
7.87
A
13.50
A
87
kW
0.65
021
026
21.60
25.80
220
250
240
280
5.13
6.41
1.88
2.16
1
1-1/4
1000
1000
126
150
1-1/4
1-1/4
1
1-1/4
8
8
1/2
1/2
3/8
3/8
3
2
52
60
1.81
1.81
500
610
5
5
2222
3278
12.91
11.05
021
026
8.57
9.56
8.72
9.75
15.50
18.80
15.75
19.10
10.8
12.23
20.00
22.50
132
134
0.68
0.89
033
31.70
285
315
7.70
2.82
1-1/4
1000
138
1-1/4
1-1/4
8
1/2
3/8
3
60
1.81
610
5
3000
10.96
033
12.39
12.60
24.55
24.95
14.95
28.00
139
0.93

Hide quick links:

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Aquasnap 30rh

Table des Matières