12 – Specifi cations
12-1 UPS System Technical Specifi cations
Input
Input Voltage
Voltage Regulation
Harmonic Distortion
PFC (Full Load)
Frequency
Frequency Tolerance
Output
Input Voltage
Output Frequency
Total Harmonic (Linear Load)
Voltage Regulation
Frequency Regulation
Overload
Audible Warning
Battery Backup
UPS Abnormal
Display
LED
LCD
Interface
Standard
Optional
Others
Parallel Redundancy
EPO
SRAM Event Log
Parameter Configuration
Hot Standby Installation
Battery Temperature Compensation
Battery Cold-Start
Overall
Efficiency
Transfer Time
Temperature
Humidity (non-condensing)
Noise (1 m)
Dimensions (Power Module)
Weight (Power Module)
* With internal batteries.
12-2 UPS System Floor Loading Table
Model
SU40K
Weight
682 kg
2
Floor Loading
1543 kg/m
1081 kg/m
Model
(Capacity)
Static
Dynamic
Interior Oscillator
Synchronized
Normal
ECO
Width
Depth
Height
SU60K
SU60KTV
SU80KTV
534 kg
534 kg
584 kg
2
2
1208 kg/m
1321 kg/m
SU40K
SU60K
(40kVA/32kW)
(60kVA/48kW)
120/208V AC, 3O,
4-wire + ground, wye
-25% ~ +20%
< 5% (Full Load)
> 0.99
50 / 60 Hz
45 ~ 65 Hz
120/208V AC, 3O,
4-wire + ground, wye
50 / 60 Hz
≤3%
±1%
±7% (10% ~ 90% Linear Load)
±0.05 Hz
±5%
≤125% : 10 minutes; ≤150% : 1 minute
Intermittent
Continuous
UPS Status: Normal • Bypass • Backup • Fault
Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage
UPS abnormal messages with intelligent self-diagnosis.
RS-232, Dry Contact
SNMPWEBCARD
Yes (1+1 for 2 UPS systems of the same type and capacity only.)
Standard (Local and Remote)
500 Records
Yes
Optional
Optional
Standard
92%
96%
0 ms
32° F ~ 104° F (0° C ~ 40° C)
90%
65 dBA
68 dBA
520 mm
850 mm
950 mm
1696 mm
682 kg*
534 kg
12-3 Battery Pack Floor Loading Table
(40 12V batteries;
Model
2
Weight
Floor Loading
51
SU60KTV
SU80KTV
(60kVA/48kW)
(80kVA/64kW)
277/480V AC, 3O,
4-wire + ground, wye
277/480V AC, 3O,
4-wire + ground, wye
70 dBA
850 mm
534 kg
BP480V26B
BP480V40C
(40 12V batteries;
26AH each)
40AH each)
470 kg
700 kg
2
1064 kg/m
1575 kg/m
1
2
3
4
5
6
7
8
9
10
70 dBA
11
584 kg
12
13
2
14