AC Output
Voltage Regulation: Regulates steady state output voltage to ±5% of nominal on line and on battery at the default
parameter settings. Exceeds the CBEMA voltage regulation guideline for computing equipment
under any line, load or battery condition, excluding bypass mode.
Sine Wave Power:
Output Frequency: 50 Hz or 60 Hz ±0.15 Hz on battery. Same as line on AC line within programmable limits. (See
Section 303, parameters 13-17).
Output Protection: Provides automatic current and overvoltage protection. The unit has high AC and low AC output
voltage alarms, as well as circuit breaker warning/shutdown and overload alarms. Optional output
receptacle panels protected by fuses or circuit breakers.
Lightning, Surge, and Noise Protection
Lightning/Surge Protection:
Surge Voltage Let-Through:
Surge Suppressor Rating:
Noise (RF) Isolation:
Isolation:
Environment
Ventilation:
Air around the UPS must be free of dust, chemicals, or other materials that corrode or contaminate.
Air must be free to move around the UPS. Do not place the UPS in a sealed room or container.
Operating Environment: 0° to + 40° Celsius (+32° to +104° F). 0 to 95% relative humidity (noncondensing). Battery
High Altitude Operation: The maximum operating ambient temperature drops 1° Celsius per 300 meters (2° Fahrenheit
Storage Temperature:
Batteries and Battery Charger
Batteries:
Batteries are sealed, maintenance-free, gas recombinant, lead-acid type, specially designed for UPS use.
Nominal battery voltage is 48 VDC. Batteries are UL 924 recognized.
Battery Charger: The standard battery charger is a three-state charger (Maintenance, Constant Current and Constant
Voltage). Recharge time to 85% is 4 to 6 hours typical.
Third Party Compliance and Standards
Safety/EMC Compliance: UL listed, cUL listed to Canadian standards, TÜV/GS certified, FCC Part 15: Class A
Applicable Standards:
Provides sine wave, computer-grade power with five percent or less total harmonic distortion at
full resistive load on battery power. Meets or exceeds CSA C22.2 No. 107.1. Output wave form
is essentially the same as line on AC line.
Passes ANSI/IEEE C62.41 Categories A3 (6000 volt, 200 amp ring-wave test) and B3
(6000 volt, 500 amp ring-wave and 6000 volt, 3000 amp combination-wave). UL 1449
listed. Meets IEC 801-5. Zero Surge Clamping Response Time.
0.7% of peak (typical) in ANSI/IEEE C62.41 1991 Category A3 test.
300 Joules.
Advanced, compound filter elements provide up to 90 dB attenuation in normal mode
from 100 KHz to 10 MHZ and up to 50 dB attenuation in common mode from 100 KHz
to 10 MHZ.
Input isolated from output. Output neutral bonded to ground.
service life is longer if the operating temperature stays below 25° Celsius (77° F).
per 1000 feet) above sea level, with the maximum operating elevation being 3000 meters
(10,000 feet).
Batteries: -20° to +40° Celsius (-4° to +104° F).
UPS without batteries: -20° to +60° Celsius (-4° to +140° F).
(includes Class A limits specified in the Radio Interference Regulations of the Canadian
Department of Communication), Vfg 243/1991, Vfg 46/1992, CISPR 22.
UL 1778, UL 1449, CSA Standard C22.2 No. 107.1-M95, BSI EN 60950, EN 50082-1,
EN 50091-1.