Unity I UT3K Manuel D'utilisation page 17

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Table 4: Parameters
Parameter
Parameter
Number
Name
P-00
Password
Auto
P-03
Restart
P-05
Nominal
Output
Voltage
Low
P-07
Runtime
Alarm
Setpoint
Frequency
P-13
P-14
Nominal
Frequency
Auto
P-15
Frequency
Enable
Maximum
P-16
Frequency
P-17
Minimum
Frequency
P-26
PhonTek™
Password Level
Sample
Required to
Parameter
Change Setting
Value
None
0
User
1
User
240
User
2
Change not
60.0
allowed
User
1
User
1
User
65.0
45.0
User
0
User
Parameter Description
Allows you to enter a password. See Section 302.
When the UPS shuts itself down, this parameter determines
whether the UPS restarts automatically. If set to "1," the UPS
restarts itself when conditions allow. If set to "0," you must
manually restart the UPS by turning the keyswitch to "Off"
and back to "Auto." Choices: 0 (Disable) or 1 (Enable).
Sets the nominal output voltage. This setting should equal the
output voltage wired at the factory or by your electrician. Call
Best Power's Worldwide Service or the nearest Best Power
office before you try to change this setting. Range of values:
180-260.
If the UPS is running on battery power, it sounds a Low
Runtime alarm (A-00) when the amount of battery runtime
remaining (in minutes) is equal to or less than this value.
Range of values: 1-99.
The frequency that the UPS is now supplying to your
equipment.
If parameter 15 = 0, this parameter allows you to choose the
unit's nominal output frequency. If the UPS is in auto
frequency mode (parameter 15 = 1), this parameter shows the
nominal frequency that the unit has selected. Choices: 0 (50
Hz) or 1 (60 Hz).
Enables auto frequency mode if set to "1." In auto frequency
mode, the UPS automatically selects the nominal frequency
based on the input frequency. Choices: 0 (Disable) or 1
(Enable). Note: If auto frequency mode is enabled, the unit
automatically selects the frequency, then automatically resets
the maximum frequency (parameter 16) to the auto-selected
frequency + 3 Hz and resets the minimum frequency
(parameter 17) to the auto-selected frequency – 3 Hz.
Sets the maximum input frequency for operation on AC line.
The value must be greater than the nominal frequency (see
parameters 14 and 15). Range of values: 50.5-65.0. Note: If
you manually set maximum frequency, disable auto frequency
mode (parameter 15).
Sets the minimum input frequency for operation on AC line.
The value must be less than the nominal frequency (see
parameters 14 and 15). Range of values: 45.0-59.5. Note: If
you manually set minimum frequency, disable auto frequency
mode (parameter 15).
In units with software version 1.04 or higher, this
parameter starts PhonTek transmission and sets the
number of copies to be sent. If you need to use PhonTek, Best
Power's Worldwide Service will provide more instructions.
Range of values: 0-98 copies. 99 = continuous.
15
E
N
G
L
I
S
H

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

I ut4kI ut5kI ut8k

Table des Matières