Fire Safety Systems; Installation; Installation Clearances - MagiCater MCF Serie Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTALLATION/OPERATION
Inspect gas pressure regulator and hose assembly before each use. If it evident that there
is excessive abrasion or wear, or the hose or regulator is cut or damaged in any way, it
must be replaced prior to the appliance being put into operation. A replacement pressure
regulator and hose assembly must be that specified by the manufacturer.

Fire Safety Systems

Your new appliance must have proper ventilation to function safely and properly. Exhaust gas temperatures can
reach as high as 1100 °F (593 °C). Therefore, it is very important to have a fire safety device readily accessible
during operation. Your ventilation system should be designed to allow for easy cleaning. The following tables
contain a list of reference documents that will provide guidance on fire safety devices. It is not necessarily
complete. Additional information can be obtained from CSA International, 8501 East Pleasant Valley Road,
Cleveland, OH, 44131 or visit their website at www.csa-international.org.
CO
Type Extinguishers
2
Dry Chemical Type Extinguishers
Water Type Extinguishers
Foam Type Extinguishers

Installation

If you have completed the above steps that are applicable to the appliance you purchased, the appliance is now
ready to be installed. Although it may be possible for you to install and set up your new appliance, it is
STRONGLY recommended that you have this done by qualified professionals. A qualified professional will
ensure that the installation is safe and meets local building and fire codes.
DO NOT obstruct the flow of combustion, ventilation or air openings around the appliance.
Adequate clearance around the appliance is necessary for servicing and proper burner
operation. Ensure that you meet the minimum clearance requirements specified in this manual.

Installation Clearances

The clearances shown below are for combustible and non-combustible installations and will allow for safe and
proper operation of your appliance.
In addition to the above clearances there must also be at least 28 in (71.2cm) of open space in front of the unit.
It is essential that the appliance be operated only when adequate ventilation is provided. Inadequate ventilation
many not properly evacuate all appliance emissions. Excessive winds may cause drafts, which could interfere
with proper operation of the pilot and burners. Never block the flue opening or locate this appliance under
overhead unprotected combustible surfaces.
A down draft will not allow the appliance to exhaust properly and will cause overheating, which
may cause permanent damage. Damage caused by down drafts will not be covered by the
warranty. NEVER allow anything to obstruct the flow of combustibles or ventilation exiting the
appliance. NEVER place anything on top of the flue area, or block the flue in any way.
Types of Fire Extinguishers
Topic
UL Document
WARNING
Combustible
Construction
Back
6 in. (15 cm)
Sides
6 in. (15 cm)
Floor
6 in. (15 cm)
CAUTION
6
National Fuel Gas
Code Document
ANSI/UL 154
ANSI/NFPA 12
ANSI/UL 299
ANSI/NFPA 17
ANSI/UL 626
ANSI/NFPA 13
ANSI/UL 8
ANSI/NFPA 11
Non-
Combustible
Construction
0
0
6 in. (15 cm)

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Mcf14Mcf18

Table des Matières