Jandy
3.2.5 Auxiliary Load Operation
The VS PlusHP is equipped with a terminal bar that
provides user access to a built-in Auxiliary Load relay
contact. This normally-open, dry contact is activated
under certain operating conditions and is primarily
intended to be used to control external devices that
require system water flow for proper functioning, such
as heaters, booster pumps, salt water chlorinators, etc.
See Figures 5 and 6 for compartment's location details.
An access cover with Phillips-head screw must be
removed before proceeding.
3.2.5.1 Auxiliary Load Connection
Requirements
WARNING
ELECTRICAL SHOCK HAZARD
Due to the potential risk of fire, electric shock, or
injuries to persons, Zodiac® Pumps must be installed
in accordance with the National Electrical Code
(NEC
), all local electrical and safety codes, and the
®
occupational Safety and Health Act (OSHA). Cop-
ies of the NEC may be ordered from the National
Protection Association, 470 Atlantic Ave., Boston,
MA 02210, or from your local government inspection
agency.
In Canada, Zodiac Pumps must be installed in accor-
dance with the Canadian Electrical Code (CEC).
The Auxiliary Load relay contacts are rated at
230V/11A RMS. Please ensure the requirements of
the equipment to be connected to the Auxiliary Load
do not exceed this rating.
1
2
F1015
TP133
TP130
/100
TP127
Earth
230V
Earth
Auxiliary
Load
Note: In this configuration, it is important to verify the shared
power source is adequately rated to service both the pump
and the auxiliary equipment.
Figure 7.
230V Auxiliary Load, Shared Power Source
Wiring Diagram
Pro Series VS PlusHP Pumps
®
®
L2 L1
F1014
L1
(Black)
230V
Power
Source
L2
(Red or
Black)
L2
(Red or Black)
EXAMPLE ONLY
NOT Representative of
all wiring configurations
|
Installation & Operation Manual
TP133
TP130
/100
TP127
Line
(Black)
115V
Power
Source
Neutral
(White)
Earth
Figure 8.
115V Auxiliary Load, Separate Power
Sources Wiring Diagram
TP133
TP130
/100
TP127
L1
(Black)
230V
Power
Source
L2
(Red or Black)
Earth
Figure 9.
230V Auxiliary Load, Separate Power
Sources Wiring Diagram
3.2.6 Auxiliary Load Operation
Characteristics
Auxiliary Load relay contact activation is speed-
dependent, and behaves as follows:
3.2.6.1 Contact Closure
From a stopped condition, there is a three-minute delay
before the Auxiliary Load contact is closed when the
motor speed reaches and maintains a speed of at least
1725 RPM.
From a running condition at below 1725 RPM, there is
a five-second delay before the Auxiliary Load contact
is closed when the motor speed reaches and maintains a
speed of at least 1725 RPM.
ENGLISH
1
2
L2 L1
F1015
F1014
(Black)
(Red or
Black)
Earth
Line
(Black)
EXAMPLE ONLY
115V
Auxiliary
NOT Representative of
Load
all wiring configurations
1
2
L2 L1
F1015
F1014
(Black)
(Red or
Black)
Earth
Line
(Black)
EXAMPLE ONLY
230V
NOT Representative of
Auxiliary
Load
all wiring configurations
Page 11
L1
230V
Power
Source
L2
L1
230V
Power
Source
L2