2
Technical data
General data and operating conditions
2
Technical data
2.1
General data and operating conditions
Mains data
Mains types
With grounded neutral (TT/TN systems)
Other mains types
Protection
Degree of protection
Insulation resistance
Leakage current
Ambient conditions
Temperature
Storage
Transport
Operation
Site altitude
Pollution
Vibration resistance
Mounting conditions
Mounting location
Mounting position
Mounting position
Free spaces
at the top
at the bottom
to the sides
32
Operation permitted without restrictions
Observe instructions for special measures in the
documentation for the basic device!
EN 60529
IP 20
EN 61800−5−1
Overvoltage category III
> 2000 m: Overvoltage category II
EN 61800−5−1
> 3.5 mA
−25 ... +60 °C
−25 ... +70 °C
−10 ... +55 °C
Current derating from +40 to +55 °C: 2.5 %/°C
0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating by 5 %/1000 m
EN 61800−5−1
Pollution degree 2
EN 50178; IEC
Acceleration−resistant up to 0.7 g
61800−5−1;
Germanischer Lloyd,
general conditions
In the control cabinet
Between mounting plate and standard device (standard) or to the left of the
standard device (for controllers in push−through technique or in cold−plate
technique)
Vertical, mains connection on top
> 150 mm
> 100 mm
> 100 mm
l
Not in the wire range of
the terminals
Observe regulations and
safety instructions!