5. Commissioning, operation
5.3 Transmitter (active)
In the case of a temperature sensor with transmitter, as a rule, the
transmitter should be operated in the middle of the measuring range,
since deviations can occur at the range limits. The ambient temperature
EN
of the transmitter electronics should be kept constant. The transmitter
must be operated at a constant supply voltage (±0.2 V). Current/voltage
spikes from switching the supply voltage on or off must be prevented by
the customer. The measuring range is altered by changing the positions
of the jumper links (see connection diagram). The initial value of the new
»
ANSCHLUSSPLAN UND KONFIGURATION
measuring range is then available after approx. 2 s.
Die Messbereichsumstellung erfolgt durch Umstecken der Jumper in spannungslosem Zustand. Der Ausgangswert im neuen Messbereich liegt
dann nach 2 Sekunden vor. Bei Typ TRA hat Jumper 2 keine Funktion.
4 ... 20 mA
0 ... 10 V or 0
... 5 V
Passiv
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Deutschland · tel: 02778/6960-0 · fax: -400 ·
16
-3 °C
[-6 °F]
-50 ... +50 °C
[-30 ... +130 °F]
0 ... 100 °C
[40 ... 240 °F]
0 ... 160 °C
[0 ... 150 °F]
Abb.: (Messbereichs- und Offseteinstellung, Standardeinstellung: 0 °C..+160 °C | 0 K)
AKF10+_Datenblatt_de.docx © 2020
WIKA operating instructions model A2G-60
+3 °C
[+6 °F]
-10 ... +120 °C
0 ... 50 °C
[0 ... 250 °F]
[40 ... 140 °F]
0 ... 250 °C
-15 ... +35 °C
[30 ... 480 °F]
[0 ... 100 °F]
-20 ... +80 °C
[40 ... 90 °F]
Abb.: (Anschlussbelegung passiver Sensor)
www.thermokon.de
Stand: 19.08.2020
·
email@thermokon.de