Dimplex WI 10TU Instructions D'utilisation Et D'installation page 32

Pompe a chaleur eau-eau pour installation interieure

Publicité

Les langues disponibles

Les langues disponibles

English
Type and order code
1
Design
Heat source
1.1
model
1.2
Contr.
1.3
Thermal energy metering
1.4
Installation location
1.5
Performance levels
2
Operating limits
2.1
Heating water flow
2.2
Cold water (heat source)
3
Flow / sound
3.1
Heating water flow at internal pressure differential
Nominal flow according to EN14511 at W10-7 / W35-30
Minimum heating water flow
3.2
Cold water flow at internal pressure differential
Nominal flow according to EN14511 at W10-7 / W35-30
Minimum cold water flow
3.3
Sound power level according to EN 12102
3.4
Sound pressure level at a distance of 1 m
4
Dimensions, connections and weight
3
4.1
Device dimensions
4.2
Weight of the transportable unit(s) incl. Packaging/full
4.3
Device connections for heating system
4.4
Device connections for heat source
4.5
Refrigeran / total filling weight
4.6
GWP value / CO
equivalent
2
4.7
Refrigeration circuit hermetically sealed
4.8
Lubricant / total filling quantity
4.9
Volume of heating water in device
4.10 Volume of heat transfer medium in device
5
Electrical connection
5.1
Supply voltage / fuse protection Compressor
5.2
Control voltage / fuse protection
5.3
Degree of protection according to EN 60 529
5.4
Starting current with soft starter
5.5
Nominal power consumption W10/W35/max. consumption
5.6
Nominal current W10/W35/cos
5.7
Power consumption of compressor protection (per compressor)
6
Complies with the European safety regulations
7
Additional model features
7.1
Water in device is protected against freezing
7.2
Max. operating overpressure (heat source/heat sink)
5
8
Heat output / COP
Heat output / COP
1. The specified sound levels apply if the supporting feet (available as an option) are not used. If the supporting feet are used, the level can deviate by up to 3dB(A).
2. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35 °C.
The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
3. Please note that additional space is required for pipe connections, operation and maintenance.
4. Flat-sealing
5. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, the bivalence point and
regulation should be taken into consideration. These specifications can only be achieved with clean heat exchangers. Information on maintenance, commissioning and oper-
ation can be found in the respective sections of the installation and operating instructions. The specified values, e.g. W10 / W35, have the following meaning: Heat source
temperature 10 °C and heating water flow temperature 35 °C.
6. See CE declaration of conformity
7. The heat circulating pump and the heat pump manager must always be ready for operation.
EN-12
at W10-7 / W45-40
at W10-7 / W55-47
at W10-7 / W45-40
at W10-7 / W55-47
1
2 1
Primary circulating pump
Joint supply
Compressor and primary circulating pump
5
7
Performance level
at W10 / W55
at W10 / W45
at W10 / W35
452235.66.21 · FD 9912
WI 18TU
Water
Universal
WPM EconPlus
Integrated
Indoors
1
°C
20 to 62 ± 2
°C
+7 to +25
m³/h / Pa
2.9 / 16200
m³/h / Pa
2.7 / 14100
m³/h / Pa
1.6 / 5100
m³/h / Pa
1.6 / 5100
m³/h / Pa
4.0 / 15200
m³/h / Pa
3.4 / 11200
m³/h / Pa
3.3 / 10500
m³/h / Pa
3.3 / 10500
44
dB(A)
32
dB(A)
840  650 x 655
H x W x D mm
kg
160
4
Thread 1¼" external
Inches
4
Thread 1¼" external
Inches
type/kg
R410A/3.4
--- / t
2088 / 7
yes
type/litres
Polyolester (POE)/1.2
Litres
4.5
Litres
2.9
3~/PE 400 V (50 Hz) / C13 A
3~/PE 400 V (50 Hz) / C10 A
3~/PE 400 V (50 Hz) / C13 A
1~/N/PE 230 V (50 Hz) / C13 A
IP 21
A
23
2.95 / 5.4
kW
A / --
5.32 / 0.8
W
thermostatically controlled
6
Yes
bar
3.0
EN 14511
1
kW / ---
15.1 / 3.6
kW / ---
15.6 / 4.4
kW / ---
17.1 / 5.8
WI 10TU - WI 22TU
WI 22TU
Water
Universal
WPM EconPlus
Integrated
Indoors
1
20 to 62 ± 2
+7 to +25
3.8 / 22900
3.6 / 20700
2.2 / 7700
2.2 / 7700
5.3 / 21400
4.7 / 17100
4.0 / 12100
4.0 / 12100
47
35
840  650 x 655
179
Thread 1¼" external
Thread 1½" external
R410A / 4.0
2088 / 8
yes
Polyolester (POE) / 1.9
5.6
3.3
3~/PE 400 V (50 Hz) / C16 A
3~/PE 400 V (50 Hz) / C10 A
3~/PE 400 V (50 Hz) / C16 A
1~/N/PE 230 V (50 Hz) / C13 A
IP 21
28
3.91/ 7.2
7.06 / 0.8
thermostatically controlled
6
Yes
3.0
EN 14511
2
1
20.0 / 3.6
21.1/ 4.4
22.3 / 5.7