Owner Orientation
This section provides generator owners with the
information necessary to achieve the most satisfactory and
cost effective installation possible.
Federal and local codes, appearance, noise levels,
fuel types, and distances are the factors that must
be considered when negotiating with an installation
professional.
Power Decrease at High Altitude or
High Temperature
Air density is less at high altitudes, resulting in less
available engine power. Specifically, engine power will
decrease 3.5% for each 1,000 feet (300 meters) above sea
level and 1% for each 10° F (5.6°C) above 77°F (25°C).
Make sure you and your installer consider these factors
when determining total generator load.
8
Remember that as the distance from the existing electrical
service and gaseous fuel supply increases, and the
number of 90 degree bends in the fuel supply increases;
compensations in piping and wiring materials must be
made. This is necessary to comply with local codes and
overcome electrical voltage drops and gaseous fuel
pressure drops.
The factors mentioned above will have a direct affect
on the overall price of your generator installation.
In some areas you may need to acquire electrical permits
for installing the home generator, building permits for
installing gas lines, and permits for noise allowances. Your
installer should check your local codes AND obtain the
permits before installing the system.