The Special Display Function; The Auto Operating Mode - Kübler CODIX 533 Mode D'emploi

Générateur de consigne
Masquer les pouces Voir aussi pour CODIX 533:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

2.The SPecial disPlay function

A
The function SPecial.decimalPoint allows defining the
number of decimal places (only for the values appea-
ring on the display).
display.Low allows defining the minimum value to be
displayed. This value corresponds to the value ou.Lo
used for the output setpoint.
display.High allows defining the maximum value to be
displayed. This value corresponds to the value ou.Hi
used for the output setpoint.
Example:
The display must show 10 (kg) while the setpoint out-
put must be 2 V (lower limit value); the display must
show 40 (kg) while the setpoint output must be 8 V
(upper limit value).
7
D
6
A
8 V
2 V
10 kg
to
to
40 kg
3. Press both keys to resume programming at point
4.2.2 (1), SiGn see A
Summary:
Display
Output value
When programming, the values for the display and for
the output setpoint are linked internally together.
Note:
When the SPecial display function is activated, the
increment relates to the value scaled in the MAn
operating mode.

4.2.3 The Auto Operating Mode

1. The following parameters can be programmed for
the Auto mode:
1 sec
in the flow chart
A
see 4.2.3.1
to
to
to
to
to
to
EN - Page 6

Publicité

Table des Matières
loading

Table des Matières