12. Control panel (if present)

KEYS AND LEDS
1
UP
2
DOWN
3
Compressor Led
4
Fan Led
5
Defrost Led
6
Alarm Led
7
ON/OFF
8
SET
Switching on and turning off
Press and hold the ON / OFF key for 5 seconds: the on / off LED will switch off / on. The display will flash for 3
seconds after which the internal cell temperature will be indicated and the refrigeration cycle will begin. During
the operating cycle, the display will show the lighting of the LED corresponding to the snowflake (n ° 5) and the
lighting of the internal fan LED. (n ° 4).
Setpoint setting
Setting the Setpoint: To view the Setpoint value, press key 8: Set will appear. Pressing key 8 again will
show the default Setpoint value on the display. To change the Setpoint value, use keys 1 and 2 within 15
seconds. To confirm the change, press key 8. With Setpoint we mean a temperature value that the product
must reach with a tolerance of 2 ° C higher.
Manual defrosting
To activate the manual defrosting, hold the button 1 for 5 seconds.
All the LEDs will turn off, except for the LED number 5: the defrosting cycle will start.
TROUBLESHOOTING
LABEL
TROUBLE
Probe 1 broken
PR1
(refrigerating
room)
Press and release - Scrolls through the menu items Increases the values
Press for at least 5 seconds - It starts the function manual defrost
Press and release - Scrolls through the Menu items Decreases the values
Steady: compressor activated
Flashing: delay, protection or blocked activation
Steady: fans activated
Steady: defrost activated
Flashing: manual activation
Steady: presence of an alarm
Flashing: alarm
Press and release - Goes up one level from the current menu confirmation parameter
value
Press for at least 5 seconds - Press and hold down the ON/OFF key for 5 sec: the
on/stand-by LED will switch off/on (when not inside the menu)
Press and release - Displays alarms (if present)
Accesses to Basic Commands Menu
CAUSE
• reading of values outside
of the operating range
• broken /short-circuit /open
probe
RESULT
•Label E1 display
•Steady Alarm led
15
SOLUTION
•Check probe type(NTC)
•Check probes wiring
• Replace the probe