Télécharger Imprimer la page

C2AI MVE5 Série Instructions De Montage page 6

Publicité

LEDs
Error
behaviour
Valve stroke
1
RED ON
less than
5mm
RED LED
quick
Stroke
blinking
2
longer than
+ GREEN
60mm
ON
Unexpected
stall
RED Quick
3
within the
Blinking
calibrated
stroke range
Stroke
RED Quick
4
longer than
Blinking
expected
RED slow
Low Power
5
Blinking
Voltage
RED slow
High Power
6
Blinking
Voltage
COMPORTEMENT DES LED STANDARD
Comportement
des LED
1
VERT
VERT
2
intermédiaire de la lecture de course
CLIGNOTANT
ROUGE ET VERT
3
CLIGNOTANT
Commande manuelle ON, les actionneurs
4
ROUGE ET VERT
Document non contractuel - Nous nous réservons le droit de faire évoluer les caractéristiques de nos produits sans préavis - FT/MVE5xx/MVE5xx-65/2020/03
Siège social Lyon
/ 9 rue de Catalogne - Parc des Pivolles - 69153 Décines Cedex / +33 (0)4 72 15 88 70 /
Agence Île de France
paris@c2ai.com
Actuator use
Automatic calibration
(DIP N. 7 OFF)
The actuator pushes/pulls 2
times (unexpected stall) trying
to remove the possible obstacle.
���������
After 2 tries an alarm is signalled
installation
and the actuator moves to initial
position and does not respond to
control signal. Stroke value is not
updated because out of range
The actuator exits the 60mm
stroke range and it moves
toward the new stroke limit
signalling an anomaly. The
actuator pushes/pulls 2 times
���������
against the new stroke limit, then
installation
it goes back to the initial position
still signalling the anomaly until it
is not within 60mm. The actuator
does not calibrate the stroke
after 10s (wrong range)
The actuator tries 5 times against
normal
the new stall condition and then
operation
after 10s the actuator updates
the new stroke length
The actuator moves toward the
Normal
new stall condition with a lower
operation
speed; after 10s the actuator
updates the new stroke value
The actuator is still working
Normal
but performance cannot be
operation
guaranteed
The actuator is still working
Normal
but performance cannot be
operation
guaranteed
État de l'actionneur
L'actionneur est arrivé au point
extrême de la lecture de course
L'actionneur est arrivé au point
L'actionneur lit la course ou va en
position initiale
ignorent le signal de commande.
ATTENTION! La carte électronique est
alimentée électriquement
Agence Est
mulhouse@c2ai.com
Actuator behaviour
Manual calibration
(DIP N. 7 ON)
The actuator pushes/pulls 2
times against endpoint during
calibration and the actuator
moves to the initial position and
then it does not respond to the
control signal. The actuator
keeps the previous stroke
The actuator exits the 60mm
stroke range and it moves
toward the new stroke limit
signalling an anomaly. The
actuator pushes/pulls 2 times
against the new stroke limit,
then it goes back to the initial
position still signalling the
anomaly until it is not within
60mm. The actuator does not
calibrate the stroke after 10s
(wrong range)
The actuator tries 5 times
against the new stall condition.
At the end of the attempts
the fault will be signalled. The
actuator does not update the
new stroke length, but after 60s
makes other attempts to verify
the stall condition
The actuator moves toward the
new stall condition with a lower
speed; after 10s the actuator
does not update the new
stroke value
The actuator is still working
but performance cannot be
guaranteed
The actuator is still working
but performance cannot be
guaranteed
STANDARD LEDs BEHAVIOUR
LED
behaviour
1
GREEN ON
GREEN
2
BLINKING
RED GREEN
3
BLINKING
4
RED GREEN ON
contact@c2ai.com
Agence Sud-Ouest
Service Export
sudouest@c2ai.com
export@c2ai.com
Typical trouble
shooting
condition
Valve with a
stroke length
lower than 5mm
Valve with a
stroke length
longer than
60mm
Valve stuck
Stem connection
loose or valve
damaged
1. Wrong
transformer size
2. Unstable power
1. Wrong
transformer size
2. Unstable power
Actuator status
The actuator arrived at the extreme point of
the stroke read
The actuator arrived at the intermediate
point of the stroke read
The actuator is reading the stroke or it is
going to initial position
Manual control ON, the actuators ignores the
control signal.
ATTENTION! The electronic board is
electrically supplied
e
contact@c2ai.com
www.c2ai.com
l
Reset
procedure
Remove
power and
power up
again
Remove
power and
power up
again
Inverted
control signal
Inverted
control signal
Correct
Voltage
Power
Correct
Voltage
Power

Publicité

loading

Ce manuel est également adapté pour:

Mve5-65 série