Installing Optional Rear Outlet
Rear outlet kit, 10" (254mm) boot assembly with register, ROK-1
for warm air discharge into an adjoining room.
Attention: Before furnace is attached to the wall, the wall opening
for the rear outlet must be cut, in addition to removal of the outer
and inner casing knockouts on furnace.
1.
The wall opening measurements for the rear outlet are the
following.
A. From floor to bottom of wall opening is 14 3/4" (375mm).
B. From bottom of wall opening to top of wall opening is 8 1/2"
(216mm) .
C. Wall opening width is 12 1/8" (308mm).
2. Remove outer casing knockout from outer casing back.
3. Remove inner casing knockout from inner casing.
4.
Attach furnace to wall (see Attaching Furnace to Wall).
5.
Align clearance holes on 8" x 12" (203mm x 305mm) boot with
screw holes on outer casing back and mark boot to be flush
with wall surface. Remove boot and cut to proper length.
6. Attach 8" x 12" (203mm x 305mm) boot to outer casing back
with (6) #10 x 1/2" (13mm) screws provided.
7.
Align clearance holes on 6" x 10" (152mm x 254mm) duct with
screw holes on inner casing and mark duct to be 2 1/4" (57mm)
shorter than 8" x 12" (203mm x 305mm) boot. Remove duct
and cut to proper length.
8.
Attach 6" x 10" (152mm x 254mm) duct to inner casing with
(6) #10 x 1/2" (13mm) screws provided.
9.
Insert rear register into 8" x 12" (203mm x 305mm) boot. Attach
rear register to wall with (2) #10 x 1" (25mm) screws provided.
ALL CONNECTIONS MUST BE MECHANICALLY
MADE AND LISTED CLERANCES MAINTAINED
2 PIECE VENT ENCLOSURE
CUT TO THE PROPER LENGTH
MOUNTING HOLE
37405-4-0519
INSTALLATION (CONT'D)
*PARTS LISTED ARE TO BE PURCHASED
LOCALLY
SPACER STRAP*
BASE PLATE*
BASE PLATE
GASKET
Figure 1
VENT CENTER TO COMBUSTIBLES
VENT CENTER TO
COMBUSTIBLES MINIMUM
MINIMUM CLEARANCE 1-9/16" (40mm)
CLEARANCE 1-9/16" (40mm)
VENT ENCLOSURE
DV-651 OR DV-665
OR DV-666
MINIMUM CLEARANCE
TO COMBUSTIBLES
18" (457mm)
REGISTER PART DV-603
6-5/8" (168mm)
WALL TO VALVE INLET
3" (76mm) TO CENTER OF
1/2" (13mm) INLET ELBOW
REAR OUTLET
REGISTER KIT #DV-637
Figure 2
(102mm)
(102mm)
(140mm)
3 1/4" (83mm)
11 ½"(292mm)
Figure 3
4" (102mm) OVAL TYPE "B"
CONNECTION
7-1/2" (191mm)
MINIMUM CLEARANCE
TOP TO COMBUSTIBLES
SIDE OUTLET
SIDE OUTLET
KIT PART DV-608
KIT PART SOK-1
4" (102mm) MINIMUM
CLEARANCE TO
FURNACE
COMBUSTIBLES
3-3/4" (95mm) FLOOR TO
CONTROL VALVE INLET
(102mm)
(140mm)
(406mm)
Figure 3A
Page 7