Empire Heating Systems FAW55IPXLP-1 Instructions D'installation Et Manuel Du Propriétaire page 13

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SERVICE & MAINTENANCE SUGGESTIONS
If the pilot does not light, or the pilot flame current is not at least 1.0
uA and steady, the module will not energize the second main valve
and the main burner will not light.
Safety Lockout
S8600H provides 100 percent shutoff, or safety lockout. A timer
starts timing the moment the trial for ignition starts. Ignition spark
continues only until the timed trial for ignition period ends. Then
the module goes into safety lockout. Lockout de-energizes the
first main valve operator and closes the first main valve in the gas
control, stopping pilot gas flow. The control system must be reset
by turning the valve off for one minute or by turning off power to the
module for one minute.
START
STAGE 1
Trial for Ignition
STAGE 2
Main Burner
Operation
END
37405-4-0519
S8600H NORMAL OPERATING SEQUENCE
Thermostat, Wall Switch,
Wall Switch, Remote, Etc.
Remote, Etc. Calls for Heat
Calls for heat
Spark Generator Powered
First Valve (Pilot)
Operator Opens
PILOT BURNER OPERATION
Pilot burner lights.
Module senses flame current.
OR
IF FLAME CURRENT SENSED
Spark generator off
Second valve operator
(Main) opens.
MAIN BURNER OPERATION
Module monitors pilot
flame current.
ON/OFF DEVICE SATISFIED
THERMOSTAT SATISFIED
Valves close. Pilot and main
Valves close. Pilot and
burners are off.
main burners are off.
Main Burner Operation
When the pilot flame is established, a flame rectification circuit
is completed between the sensor and burner ground. The flame
sensing circuit in the module detects the flame current, shuts off
the spark generator and energizes the second main valve operator.
The second main valve opens and gas flows to the main burner,
where it is ignited by the pilot burner. The flame current also holds
the safety lockout timer in the reset (normal) operating condition.
When the call for heat ends, both main valve operators are de-
energized, and both main valves in the gas control close.
CAUTION: Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
POWER INTERRUPTION
System shuts off. Restarts when
power is restored.
PILOT FLAME FAILURE
Second main operator closes.
Module starts trial for ignition.
Pilot burner does not light
MODULE
RESPONSE
S8600H
After 90 seconds*pilot valve
closes, spark stops.
* Lockout timing is stamped on module.
Page 13

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Faw55ipxnat-1

Table des Matières